2.3.  TROUBLESHOOTING

2.3.1. Failure Codes Table

Error

Code

Description of the Error

Malfunction

Probable Cause

Solution(s)

E 01

Intervention of exhaust 

Thermostat (Open 

Combustion Chamber 

boiler )

Boiler does not work,

E01 error code flashing on

the screen

> Flue Sensor faulty

1-) Reset & Restart boiler

2-) Call for authorised service at first

E 02

Low water pressure in the

system/system parameter

wrongly setted

Boiler does not work,

E02 error code flashing

on the screen

> Water pressure in the boiler not 

enough

1-) Fill the boiler 1,2-1,5 bar according to manual

2-) Check if the system pressure 1,2 - 1,5 bar from the manometer 

located right & bottom of the boiler

3-) If problem persist Call for authorised service

4-) Reset & Restart boiler

E 03

High water pressure in

the system

Boiler does not work,

E03 error code flashing

on the screen

> High Water pressure in the

boiler higher than > 2,8 bar

1-) Call for authorised service at first

2-) Check intermittent contacts or open contacts on harness carefully

3-) Check Domestic heating water temperature sensor ressistance 

according to page 95 at section 4.30 if its out of tolerance replace 

NTC

4-) Check Cabling and connectors between double NTC and board

5-) Reset & Restart boiler

E 04

Domestic heating water

temperature sensor faulty

Boiler does not work on

DHW mode but still work

on Central heating mode,

E04 error code flashing on

the screen

> Domestic heating water

temperature sensor faulty

1-) Call for authorised service

E 05

Central heating FLOW

temperature sensor faulty

Boiler does not work,

E05 error code flashing

on the screen

> Central heating FLOW

temperature sensor faulty

1-) RESET boiler at first check if problem removed

2-) Check other gas devices if they are working

3-) Check main gas suppy valve is open or not

4-) Check boiler gas suppy valve bellow the boiler is open or not

5-) RESET boiler at first check if problem removed

6-) Call for authorised service at first

E 06

No ignition

Boiler does not work,

E06 error code flashing

on the screen

> Gas supply failure

1-) RESET boiler at first check if problem removed

2-) Check boiler central heating valves are open if they are closed 

open all

3-) Check all radiator valves are open if they are closed open 

minimum 3 meters of radiator must be open

4-) RESET boiler and check if problem removed

5-) Call for authorised service at first

E 07

Safety thermostat 

intervention

Boiler does not work,

E07 error code flashing

on the screen

> Lack of water on the system

> Pump blockage

> Pump failure

> Pump harness

> Installation blockage

1-) RESET boiler at first check if problem removed

2-) Check boiler central heating valves are open if they are closed 

open all

3-) Check all radiator valves are open if they are closed open 

minimum 3 meters of radiator must be open

4-) RESET boiler and check if problem removed

5-) Call for authorised service at first

E 08

Flame circuit failure

False flame signal from

combustion or electrode

> Water blokage on syphon

> Electronic board

1-) Call for authorised service

E 09

No water circulation

in the system

Boiler does not work,

E09 error code flashing

on the screen

> Lack of water on the system

> Pump blockage

> Pump failure

> Pump harness

> Installation blockage

1-) RESET boiler at first check if problem removed

2-) Check boiler central heating valves are open if they are closed 

open all

3-) Check all radiator valves are open if they are closed open 

minimum 3 meters of radiator must be open

4-) RESET boiler and check if problem removed

5-) Call for authorised service at first

E 10

Central heating 

temperature RETURN 

sensor faulty

Boiler does not work,

E10 error code flashing

on the screen

> Central heating RETURN 

temperature sensor faulty

1-) Call for authorised service

E 11

Gas valve modulator

disconnected

Boiler does not work,

E11 error code flashing

on the screen

> Gas valve harness

1-) Call for authorised service

2-) Check gas valve cabling between board and gas valve

DHW temperature Probe,

in storage tank mode, fault

Boiler does not work,

E12 error code flashing

on the screen

> Domestic heating water 

temperature sensor in storage tank 

faulty

1-) Call for authorised service at first

2-) Check intermittent contacts or open contacts on harnesscarefully

3-) Check Domestic heating water temperature sensor ressistance

4-) Check Cabling and connectors between NTC and board

5-) Reset & Restart boiler

E 13

Exhaust temperature 

probe over-temperature 

alarm

Boiler does not work,

E13 error code flashing

on the screen

> Over temperature flue gas outlet

value > 105 C°

1-) Call for authorised service

E 14

Exhaust ( FLUE )

temperature probe fault

Boiler does not work,

E14 error code flashing

on the screen

> Central heating FLUE temperature

sensor faulty

1-) Reset & Restart boiler

2-) Call for authorised service

E 15

Fan failure (feedback/

supply)

Boiler does not work,

E15 error code flashing

on the screen

> Fan harness

1-) Reset & Restart boiler

2-) Call for authorised service

E 16

Central heating 

temperature RETURN 

sensor faulty

Boiler does not work,

E10 error code flashing

on the screen

> Central heating RETURN 

temperature sensor faulty

1-) Reset & Restart boiler

2-) Call for authorised service

E 17

Temperature difference

between FLOW and LIMIT 

NTC (Double Heating 

Probe) faulty

FLOW and LIMIT sensor

(DOUBLE NTC) 

malfunction

> FLOW and LIMIT Sensor

( double NTC ) faulty

1-) Reset & Restart boiler

2-) Call for authorised service

Содержание ENERWA

Страница 1: ......

Страница 2: ......

Страница 3: ......

Страница 4: ......

Страница 5: ......

Страница 6: ...iately evacuate the place with gas odour Natural Gas Emergency Line from your neighbour or another suitable place Do not make any intervention on installation Never close culverts ensuring discharge o...

Страница 7: ...7 warmhaus com...

Страница 8: ...blocked If a room thermostat or control device is connected ensure that it is at ON position If you will shut off the combi boiler for a long period perform below written operations Discharge the radi...

Страница 9: ......

Страница 10: ...ockwise or decreases when rotated counter clockwise The adjusted value shall be confirmed after flashing for 4 5 seconds after releasing the button and continues to display the temperature value in th...

Страница 11: ......

Страница 12: ......

Страница 13: ......

Страница 14: ......

Страница 15: ...heck if problem removed 2 Check boiler central heating valves are open if they are closed open all 3 Check all radiator valves are open if they are closed open minimum 3 meters of radiator must be ope...

Страница 16: ...E 42 Buttons anomaly Boiler does not work E42 error code flashing on the screen Wrong parameters settled on TsP menu 1 Call For service E 43 Opentherm communication error Boiler does not work E43 err...

Страница 17: ...lokage on flue or wrong flue Electrode position Cabling disconnections Combustion calibration Electronic board Gas valve failure 1 Reset Restart boiler 2 Call for authorised service E 92 Air compensat...

Страница 18: ...y valve discharge should be connected to a discharge funnel Otherwise safety valve shall be activated and manufacturer shall not be responsible due to water discharge to the place of device 0 3 2 1 0...

Страница 19: ...over time you must at least execute maintenance operations on a yearly basis in compliance with what is stated in the relative point at annual check and maintenance of the appliance in compliance with...

Страница 20: ......

Страница 21: ...lgesi Park Cadde No 10 10 05 2016 www warmhaus com tr Par a Ad Nil fer BURSA TURKEY Malzeme Tarih Date izen Drawn TAR H REV NO A IKLAMA Kontrol Approved Onay Drawn aut REV Z YAPAN All rights reserved...

Страница 22: ......

Страница 23: ......

Страница 24: ......

Отзывы: