11.7.2 Engineer Parameter List
Parameter number
Description
Units
Range
Default Value
P 00
CH Anti-Cycle time
mins
0-10
0
P 01
CH Pump Overrun time
secs
0-240
60
P 02
DHW Pump Overrun time
secs
0-240
0
P 03
DHW min flowrate
l/min/10
15-40
15
P 04
CH Pump Speed
%
50-100
100
P 05
DHW Tank Pump Speed
%
50-100
100
P 06
DHW Programmer Type
N/A
0-1
0
P 07
CH Programmer Type
N/A
0-1
0
P 08
DHW Tank setpoint offset
°C
0-30
6
P 09
DHW Tank Differential
°C
1-10
6
P 10
CH Temp Differential
°C
2-10
5
P 11
Low pressure shutdown
bar/10
2-10
6
P 12
High pressure shutdown
bar/10
24-28
28
Detailed descriptions of the Engineer Parameters can be found below:
Parameter
Description
P00
Used to prevent the burner firing in CH mode for a period after it last
stopped, to prevent inefficient short cycling of the burner CH mode.
P01
Keeps the circulating pump running for a period after the last CH cycle, to
distribute heat within the primary heat exchanger after a CH cycle.
P02
Keeps the circulating pump running for a period after the last DHW cycle,
to distribute heat within the primary heat exchanger after a DHW cycle.
P03
Minimum DHW flow rate for activation of the DHW Instantaneous cycle,
measured in litres/minute/10. For example P03=15, means 1.5
litres/minute.
P04
Circulating pump speed during CH cycle, this can be reduced depending
on system requirements.
P05
Circulating pump speed during DHW Tank cycle, this should be kept at
100% for fastest tank re-heat.
P06
DHW Programmer Type. 0 = External Time Programmer Control
1 = Internal Time Programmer Control
P07
CH Programmer Type. 0 = External Time Programmer Control
1 = Internal Time Programmer Control
P08
Temperature above DHW setpoint the Tank Cycle switches off at.
P09
Temperature differential on DHW Tank cycle.
P10
Temperature differential on CH cycle.
P11
Minimum allowable system water pressure in bar/10. For example P11=6,
means 0.6 bar.
P12
Maximum allowable system water pressure in bar/10. For example
P12=28, means 2.8 bar.
8
Perfector 8 Side:Back
Cyan
Magenta
Yellow
Black
M1
M2
Содержание Agentis B Series
Страница 2: ......
Страница 30: ...Page 29 4 5 Components 4 5 1 B Series Boilerhouse Casing Key Components...
Страница 31: ...Page 30 4 5 2 I Series Internal Casing 21 26 33 Models 44 Models...
Страница 32: ...Page 31 4 5 3 I Series Internal Key Components 21 26 33 Models 44 Models...
Страница 33: ...Page 32 4 5 4 I Series Internal Pump Group 21 26 33 Models 44 Models...
Страница 34: ...Page 33 4 5 5 I Series Internal System Components SK3 4 5 6 I Series Internal Combination Boiler Key Components...
Страница 35: ...Page 34 4 5 7 E Series External Casing 21 26 33 Models 44 Models...
Страница 36: ...Page 35 4 5 8 E Series External Key Components 21 26 33 Models 44 Models...
Страница 37: ...Page 36 4 5 9 E Series External Pump Group 21 26 33 Models 44 Models...
Страница 39: ...Page 38 4 5 12 Combination Boiler Pipe Layout...
Страница 41: ...Page 40 5 1 2 I Series Internal I21 I26 I33 5 1 3 I Series Internal I44...
Страница 42: ...Page 41 5 1 4 I Series Internal Combination Boilers I21C I26C I33C 5 1 5 E Series External E21 E26 E33...
Страница 43: ...Page 42 5 1 6 E Series External Base Tray E21 E26 E33 5 1 7 E Series External E44...
Страница 44: ...Page 43 5 1 8 E Series External E44 Base Tray 5 1 9 E Series External Combination Boilers E21C E26C E33C...
Страница 45: ...Page 44 5 1 10 E Series External Combination Boiler Base Tray E21C E26C E33C...
Страница 60: ...Page 59 6 3 2 Wiring Diagram Fuses The appliance must have a permanent live supply connected to operate...
Страница 61: ...Page 60 6 3 3 External 230V Two Channel Programmer Room Thermostat Optional Outdoor sensor...
Страница 62: ...Page 61 6 3 4 Internal Two Channel Programmer and Room Thermostat Optional Outdoor Sensor...
Страница 73: ...Page 72 6 6 9 Honeywell Y Plan Independent CH DHW Fully Pumped Only 2 CHANNEL TIMECLOCK...
Страница 74: ...Page 73 6 6 10 Honeywell S Plan Independent CH DHW Fully Pumped Only 2 CHANNEL TIMECLOCK...
Страница 93: ...Page 92 Kabin Pak External Plume Management Kit KPMK The kit comprises...
Страница 107: ...Page 106 11 4 Burner Start Up Cycle Lock out is indicated by a lamp on the control box...
Страница 122: ...Page 121 14 SPARES 14 1 RDB 2 2 BX Spares...
Страница 124: ...Page 123 14 2 RDB 3 2 BX Spares...
Страница 134: ...Page 133 Intentionally left blank...
Страница 135: ......