8.2 Flue Terminal Locations
MINIMUM DISTANCES TO TERMINALS IN MILLIMETRES AS MEASURED FROM THE
TOP OF THE CHIMNEY OR THE RIM OF A LOW LEVEL DISCHARGE OPENING
A
Directly below an opening, air brick, opening window etc.
600
B
Horizontally to an opening, air brick, opening window etc.
600
C
Below a gutter, eaves or balcony with protection.
75
D
Below a gutter or a balcony without protection.
600
E
From vertical sanitary pipework.
300
F
From an internal or external corner, surface or boundary alongside the
terminal.
300
G
Above ground or balcony level.
300
H
From a surface or a boundary facing the terminal.
600
J
From a terminal facing the terminal.
1200
K
Vertically from a terminal on the same wall.
1500
L
Horizontally from a terminal on the same wall.
750
M
Above the highest point of an intersection with the roof.
600
N
From a vertical structure on the side of the terminal.
750
O
Above a vertical structure less than 750mm from the side of the terminal.
600
P
From a ridge terminal to a vertical structure on the roof.
1500
These are minimum dimensions and are only quoted as guidelines.
Installation in exposed positions is not recommended. Account must be made of
the pluming from the flue. If it is likely to be a nuisance to the householder the use
of a vertical balanced flue or conventional flue should be considered.
Terminating positions must be at least 1.8 metres from an oil storage tank unless
a wall with at least 30 minute fire resistance and extending 300 mm higher and
wider than the tank is provided between the tank and the terminating position.
Содержание Agentis B Series
Страница 2: ......
Страница 30: ...Page 29 4 5 Components 4 5 1 B Series Boilerhouse Casing Key Components...
Страница 31: ...Page 30 4 5 2 I Series Internal Casing 21 26 33 Models 44 Models...
Страница 32: ...Page 31 4 5 3 I Series Internal Key Components 21 26 33 Models 44 Models...
Страница 33: ...Page 32 4 5 4 I Series Internal Pump Group 21 26 33 Models 44 Models...
Страница 34: ...Page 33 4 5 5 I Series Internal System Components SK3 4 5 6 I Series Internal Combination Boiler Key Components...
Страница 35: ...Page 34 4 5 7 E Series External Casing 21 26 33 Models 44 Models...
Страница 36: ...Page 35 4 5 8 E Series External Key Components 21 26 33 Models 44 Models...
Страница 37: ...Page 36 4 5 9 E Series External Pump Group 21 26 33 Models 44 Models...
Страница 39: ...Page 38 4 5 12 Combination Boiler Pipe Layout...
Страница 41: ...Page 40 5 1 2 I Series Internal I21 I26 I33 5 1 3 I Series Internal I44...
Страница 42: ...Page 41 5 1 4 I Series Internal Combination Boilers I21C I26C I33C 5 1 5 E Series External E21 E26 E33...
Страница 43: ...Page 42 5 1 6 E Series External Base Tray E21 E26 E33 5 1 7 E Series External E44...
Страница 44: ...Page 43 5 1 8 E Series External E44 Base Tray 5 1 9 E Series External Combination Boilers E21C E26C E33C...
Страница 45: ...Page 44 5 1 10 E Series External Combination Boiler Base Tray E21C E26C E33C...
Страница 60: ...Page 59 6 3 2 Wiring Diagram Fuses The appliance must have a permanent live supply connected to operate...
Страница 61: ...Page 60 6 3 3 External 230V Two Channel Programmer Room Thermostat Optional Outdoor sensor...
Страница 62: ...Page 61 6 3 4 Internal Two Channel Programmer and Room Thermostat Optional Outdoor Sensor...
Страница 73: ...Page 72 6 6 9 Honeywell Y Plan Independent CH DHW Fully Pumped Only 2 CHANNEL TIMECLOCK...
Страница 74: ...Page 73 6 6 10 Honeywell S Plan Independent CH DHW Fully Pumped Only 2 CHANNEL TIMECLOCK...
Страница 93: ...Page 92 Kabin Pak External Plume Management Kit KPMK The kit comprises...
Страница 107: ...Page 106 11 4 Burner Start Up Cycle Lock out is indicated by a lamp on the control box...
Страница 122: ...Page 121 14 SPARES 14 1 RDB 2 2 BX Spares...
Страница 124: ...Page 123 14 2 RDB 3 2 BX Spares...
Страница 134: ...Page 133 Intentionally left blank...
Страница 135: ......