10.2.5 Pressure Relief Valve
Any pressure relief valve fitted to the boiler or system must be able to discharge externally to a
drain where the discharge can be seen but cannot cause any injury or damage. No other valves
should be positioned between the relief valve and discharge termination. The pressure relief
valve should be manually activated periodically in order to assess valve opening, normally as
part of servicing.
10.2.6 Low Pressure Switch
Where there is a catastrophic loss of water from the system the boiler thermostats may fail to
operate which would result in serious damage to the appliance. To prevent this it is
recommended that a low pressure cut out switch set at 0.3 bar is fitted to
the system
and wired
in series with the boiler limit thermostat. Combination Boiler models are factory-fitted with a low
system pressure shutdown as standard.
10.3 Combination Boiler Domestic Hot Water
10.3.1 Mains Water Pressure
To protect the appliance and to prevent excessive flow rates, a pressure reducing valve is
factory-fitted to limit the maximum supply pressure to 3 bar.
A mini expansion vessel is factory-fitted after the pressure reducing valve in order to protect the
appliance from the expansion due to heating of the water in the domestic hot water pipework.
Depending on DHW system volume, additional expansion may be required.
We strongly advise that all installation pipework is run in copper. However, if plastic pipe or
plastic coated pipe is used, it must be recommended by the pipe manufacturer for use with oil
fired appliances and, in any case, the last 1000mm of pipework connected directly to the
appliance must be of copper.
Note that the flow rate from individual taps is dependent on the number of outlets being
operated together, as well as the length and size of pipework and the mains supply pressure.
10.3.2 Water Hardness
Although many of the DHW components are designed to resist lime scale formation, in areas of
hard water it may still be necessary to fit an inline chemical water softener. For further
information contact Warmflow and your local water company.
10.3.3 Boreholes
In order to minimise the pressure variations it is recommended that the differential setting on the
borehole pump pressure control is kept as low as possible without adversely affecting the pump
motor. The accumulator must be as large as possible in order to reduce the rate of pressure
change and a pressure reducing valve (PRV) must be situated between the pump and
accumulator and the boiler. The PRV must be set slightly below the minimum setting of the
pressure switch on the pump.
Содержание Agentis B Series
Страница 2: ......
Страница 30: ...Page 29 4 5 Components 4 5 1 B Series Boilerhouse Casing Key Components...
Страница 31: ...Page 30 4 5 2 I Series Internal Casing 21 26 33 Models 44 Models...
Страница 32: ...Page 31 4 5 3 I Series Internal Key Components 21 26 33 Models 44 Models...
Страница 33: ...Page 32 4 5 4 I Series Internal Pump Group 21 26 33 Models 44 Models...
Страница 34: ...Page 33 4 5 5 I Series Internal System Components SK3 4 5 6 I Series Internal Combination Boiler Key Components...
Страница 35: ...Page 34 4 5 7 E Series External Casing 21 26 33 Models 44 Models...
Страница 36: ...Page 35 4 5 8 E Series External Key Components 21 26 33 Models 44 Models...
Страница 37: ...Page 36 4 5 9 E Series External Pump Group 21 26 33 Models 44 Models...
Страница 39: ...Page 38 4 5 12 Combination Boiler Pipe Layout...
Страница 41: ...Page 40 5 1 2 I Series Internal I21 I26 I33 5 1 3 I Series Internal I44...
Страница 42: ...Page 41 5 1 4 I Series Internal Combination Boilers I21C I26C I33C 5 1 5 E Series External E21 E26 E33...
Страница 43: ...Page 42 5 1 6 E Series External Base Tray E21 E26 E33 5 1 7 E Series External E44...
Страница 44: ...Page 43 5 1 8 E Series External E44 Base Tray 5 1 9 E Series External Combination Boilers E21C E26C E33C...
Страница 45: ...Page 44 5 1 10 E Series External Combination Boiler Base Tray E21C E26C E33C...
Страница 60: ...Page 59 6 3 2 Wiring Diagram Fuses The appliance must have a permanent live supply connected to operate...
Страница 61: ...Page 60 6 3 3 External 230V Two Channel Programmer Room Thermostat Optional Outdoor sensor...
Страница 62: ...Page 61 6 3 4 Internal Two Channel Programmer and Room Thermostat Optional Outdoor Sensor...
Страница 73: ...Page 72 6 6 9 Honeywell Y Plan Independent CH DHW Fully Pumped Only 2 CHANNEL TIMECLOCK...
Страница 74: ...Page 73 6 6 10 Honeywell S Plan Independent CH DHW Fully Pumped Only 2 CHANNEL TIMECLOCK...
Страница 93: ...Page 92 Kabin Pak External Plume Management Kit KPMK The kit comprises...
Страница 107: ...Page 106 11 4 Burner Start Up Cycle Lock out is indicated by a lamp on the control box...
Страница 122: ...Page 121 14 SPARES 14 1 RDB 2 2 BX Spares...
Страница 124: ...Page 123 14 2 RDB 3 2 BX Spares...
Страница 134: ...Page 133 Intentionally left blank...
Страница 135: ......