13 COMBINATION BOILER FAULT FINDING
WARNING: The Combination Boiler fault finding tables (Central Heating and Hot Water) are
to only be used by competent and suitably qualified engineers. It may be necessary to
check live terminals inside the control panel. Extreme care should be taken when doing
so.
13.1 Error codes displayed on the LCD.
Combination Boilers are fitted with diagnostic functions that monitor the correct function of
certain control systems within the appliance.
Error codes are displayed on the LCD, a list of Error codes, their possible causes and
corrective actions are detailed below.
Code Description
Possible Cause (s)
Corrective Action (s)
E01
Burner Lockout
No fuel supply to burner, air in fuel lines
Burner fault
Consult Service Engineer
E02
High Limit
Air Lock in boiler, displaced NTC
Temperature Sensor, circulation problem
Consult Service Engineer
E04
Low System
Pressure
System not topped up after pressure loss
after bleeding radiators etc.
Leak in heating system
Check system pressure, see
Section 1.3, 1.4 & 1.5 then, check
corrosion inhibitor concentration.
E05
Boiler NTC Error Boiler Flow NTC Temperature Sensor
short circuit or disconnected
Consult Service Engineer
E06
DHW Flow NTC
Error
DHW Flow NTC Temperature Sensor
short circuit or disconnected
Consult Service Engineer
E11* Tank Limit
Displaced Tank NTC Temperature
Sensor Probe
Consult Service Engineer
E12
Tank Control
NTC Error
Tank Control NTC Temperature Sensor
short circuit or disconnected
Consult Service Engineer
E15* CH Return NTC
Error
CH Return NTC Temperature Sensor
short circuit or disconnected
Consult Service Engineer
E22
Flash Data
Corrupted
PCB Fault
Consult Service Engineer
E31
Remote Control
Communication
Error
Damaged Remote Control cable
Remote Control Fault
Consult Service Engineer
E32
MMI - Control
PCB Error (On
Remote Control)
Damaged cable in control panel
PCB Fault
Consult Service Engineer
E46
System
Pressure
Sensor Error
System Pressure Sensor disconnected
System Pressure Sensor Fault
Consult Service Engineer
E48
High System
Pressure
Filling Loop left connected, and open
Insufficient system expansion capacity
Consult Service Engineer
E62
MMI - Control
PCB Error (On
Boiler)
Damaged cable in control panel
PCB Fault
Consult Service Engineer
9
Содержание Agentis B Series
Страница 2: ......
Страница 30: ...Page 29 4 5 Components 4 5 1 B Series Boilerhouse Casing Key Components...
Страница 31: ...Page 30 4 5 2 I Series Internal Casing 21 26 33 Models 44 Models...
Страница 32: ...Page 31 4 5 3 I Series Internal Key Components 21 26 33 Models 44 Models...
Страница 33: ...Page 32 4 5 4 I Series Internal Pump Group 21 26 33 Models 44 Models...
Страница 34: ...Page 33 4 5 5 I Series Internal System Components SK3 4 5 6 I Series Internal Combination Boiler Key Components...
Страница 35: ...Page 34 4 5 7 E Series External Casing 21 26 33 Models 44 Models...
Страница 36: ...Page 35 4 5 8 E Series External Key Components 21 26 33 Models 44 Models...
Страница 37: ...Page 36 4 5 9 E Series External Pump Group 21 26 33 Models 44 Models...
Страница 39: ...Page 38 4 5 12 Combination Boiler Pipe Layout...
Страница 41: ...Page 40 5 1 2 I Series Internal I21 I26 I33 5 1 3 I Series Internal I44...
Страница 42: ...Page 41 5 1 4 I Series Internal Combination Boilers I21C I26C I33C 5 1 5 E Series External E21 E26 E33...
Страница 43: ...Page 42 5 1 6 E Series External Base Tray E21 E26 E33 5 1 7 E Series External E44...
Страница 44: ...Page 43 5 1 8 E Series External E44 Base Tray 5 1 9 E Series External Combination Boilers E21C E26C E33C...
Страница 45: ...Page 44 5 1 10 E Series External Combination Boiler Base Tray E21C E26C E33C...
Страница 60: ...Page 59 6 3 2 Wiring Diagram Fuses The appliance must have a permanent live supply connected to operate...
Страница 61: ...Page 60 6 3 3 External 230V Two Channel Programmer Room Thermostat Optional Outdoor sensor...
Страница 62: ...Page 61 6 3 4 Internal Two Channel Programmer and Room Thermostat Optional Outdoor Sensor...
Страница 73: ...Page 72 6 6 9 Honeywell Y Plan Independent CH DHW Fully Pumped Only 2 CHANNEL TIMECLOCK...
Страница 74: ...Page 73 6 6 10 Honeywell S Plan Independent CH DHW Fully Pumped Only 2 CHANNEL TIMECLOCK...
Страница 93: ...Page 92 Kabin Pak External Plume Management Kit KPMK The kit comprises...
Страница 107: ...Page 106 11 4 Burner Start Up Cycle Lock out is indicated by a lamp on the control box...
Страница 122: ...Page 121 14 SPARES 14 1 RDB 2 2 BX Spares...
Страница 124: ...Page 123 14 2 RDB 3 2 BX Spares...
Страница 134: ...Page 133 Intentionally left blank...
Страница 135: ......