Page 37
3.4.5 Freeze Protection
Freeze protection works in a number of ways depending on the current operation and conditions
at the unit. When the unit is running, freeze protection is enabled if the outlet water temperature
is more than 2°C below the inlet water temperature and is also less than 5°C. This may be the
case if the unit is trying to defrost but there is not enough energy in the heating system to utilise.
When these conditions are met, the unit will stop the compressor but continue to run the
circulating pump. The unit will exit this freeze protection mode when the outlet water temperature
rises above 7°C and the suction pressure in the refrigeration circuit is above 0bar.
NOTE: If this type of Freeze Protection is triggered 3 times within 30 minutes, the unit will
not start up. Power to the unit needs to be turned OFF and then back ON in order to
perform a reset and confirm that everything is OK with the system. The unit will start up
and operate as normal after this reset.
When the unit is not running or in standby mode, there are two stages of freeze protection built
into the unit. In the first stage, if the temperature of the heating medium falls below 4°C within the
unit and the ambient temperature is less than 0°C, the unit will automatically start up the
circulating pump to increase the medium temperature and prevent it from freezing. Therefore the
unit needs to have a permanent electricity supply and be connected to a heating system which
can always provide a complete circuit in order to achieve the minimum heating flow rate. The unit
will exit freeze protection mode when the heating medium temperature rises above 8°C or the
ambient temperature rises above 1°C.
In the second stage, if the temperature of the heating medium falls below 2°C within the unit and
the ambient temperature is less than 0°C, the unit will automatically start up the compressor and
run in heating mode to increase the medium temperature and prevent it from freezing. Again, the
unit needs to have a permanent electricity supply and be connected to a heating system which
can always provide a complete circuit in order to achieve the minimum heating flow rate. The unit
will exit freeze protection mode when the heating medium temperature rises above 15°C or the
ambient temperature rises above 1°C.
3.4.6 Heating Circuit Line Components
Together with the heating system, associated pipework and manifolds, the heating circuit will also
require the following items, expansion vessel, strainer/filter, filling loop, drain valve, pressure
gauge, pressure relief valve and isolation valves. A full flow 3-port motorised valve may also be
required for some systems; this can be ordered separately, please contact Warmflow for details.
Please see section 3.9 for more details of installing and wiring the 3-port motorised valve. These
air source heat pump units come with the following items included integrally, a high flow circulating
pump, a manual air vent, flow switch and temperature sensors. A strainer/filter, isolating valves,
elbows and a set of flexible hoses are also supplied with the units as standard.
Содержание A Series
Страница 36: ...Page 34 Figure 24 AS02 R32 Casing Dimensions Heating Connection Locations FRONT SIDE TOP...
Страница 40: ...Page 38 Figure 26 Heating DHW Schematic Figure 27 Heating Only Schematic...
Страница 70: ...Page 68 7 APPENDIX B WIRING DIAGRAMS...
Страница 71: ...Page 69...
Страница 72: ...Page 70 This page is intentionally left blank...
Страница 74: ...Page 72 This page is intentionally left blank...
Страница 76: ...Page 74...
Страница 77: ...Page 75...
Страница 78: ...Page 76...
Страница 79: ...Page 77...
Страница 80: ...Page 78...
Страница 81: ...Page 79...
Страница 82: ...Page 80...
Страница 83: ...Page 81...
Страница 84: ...Page 82...
Страница 85: ...Page 83...
Страница 86: ...Page 84...
Страница 87: ...Page 85...
Страница 88: ...Page 86...