7.2.1.11 elay CLOA
To prevent the sun shading product from being raised immediately at each
brightness change (e.g. when the sun is temporarily covered by a cloud), a
delay time can be assigned to the “CLOUD” limit value. This quiets the mo-
tion behaviour of the sun shading product, thereby increasing the level of
comfort. If the values reach or drop below the limit values for the duration of
this delay time, an “Up” command is triggered and the sun shading product
is raised. The setting range is 0...99 minutes.
Turn the touch wheel to set the value “Delay CLOUD”.
A setting of “0 Min.” deactivates the delay, the [
Stand.
] function button sets
the “Delay CLOUD” value to the factory setting.
7.2.1.12 Position CLOA
The “CLOUD” position value specifies the position to which a sun shading
product is to be moved in case of sunshine. The setting range is 0-100%; a
value of 0% corresponds to the upper limit position and a value of 100% to
the lower limit position.
Turn the touch wheel to set the value “Position CLOUD”.
The [
---
] function button leaves the position unchanged; the [
Stand.
] func-
tion button sets the “CLOUD Position” value to the factory setting.
7.2.1.13 Slat angle CLOA
This setting is required when you have chosen a slat product as channel type
(external or internal venetian blinds). If you have connected a slat product
(such as an external venetian blind), you can specify how the slats are to be
set after the movement to the "CLOUD" position has been completed. This
is especially useful if you prefer a specific setting. In addition, you must no
longer tilt the slats manually after automatic movement. The sun control tilts
the slats automatically if programmed accordingly.
The factory setting for the slat position with automatic operation is -80°.
To set the “Slat angle CLOUD” value, turn the touch wheel (the value increas-
es or reduces depending on the direction of rotation).
The function button [
---
] leaves the slat angle unchanged; the function but-
ton [
Stand.
] sets the value for the “Slat angle CLOUD” to -80° (factory set-
tings).
7.2.1.14 Limit values of the sun
control
To ensure proper functioning of the automatic sun control in conjunction with
the limit value "CLEAR", the following comments must be observed when set-
ting the limit values "SUN", "CLEAR" and "CLOUD":
NOTE
The value for "CLOUD" must always be the smallest value, e.g. 5 klx. The
value for "SUN" must always be the greatest value, e.g. 30 klx. If used, the
value for "CLEAR" must be set in between, e. g. 10 klx.
To find the optimal setting for your sun shading product, you should test dif-
ferent values on a bright day with changing cloud cover. This is the only way
to achieve the optimal result.
Sun control