27
for the chimney sweep and be properly insulated against condensation. The line
should not be longer than 4 m and not have more than 3 bends. If the line leads out-
doors, it should be provided with a suitable windbreak and fly screen.
General information on the subject of room air dependent or room air inde-
pendent operation:
The stove is supplied as a standard room air-dependent fireplace stove. This means
that the stove draws all of the combustion air from the installation room via the central
air intake on the back. A sufficient supply of combustion air (at full load approx. 25m³ /
h) is absolutely necessary.
In combination with ventilation and air conditioning systems (e.g. controlled ventilation
systems, fume hoods, etc.), Section 4 of the Firing Ordinance (FeuVO) is decisive in
Germany. The flue gas routing must be monitored by special safety devices (e.g. via
an approved differential pressure monitor) or, if a ventilation system is used, this must
ensure that no negative pressures greater than 4 Pa occur in the installation room
compared to the outside and that the necessary combustion air (approx. 25 m3 / h) for
the fireplace.
Please always observe - in consultation with your authorized district chimney sweep -
the applicable local regulations and rules. We cannot accept any liability for changes
made after this manual has been printed. We reserve the right to change without no-
tice.
The above-mentioned safety devices are not a substitute for professional planning
and design of an adequate combustion air supply.
As part of the acceptance, the district chimney sweep must check the adequate com-
bustion air supply / overall installation.
2.6 Choice of flue gas and air connection placement
The following steps must be observed when converting the flue gas connection:
1. Drill out the existing
3mm holes with a 6mm
drill (6x)
2. Place a standard 150mm 90° exhaust
pipe bend on the smoke tube end from
stove
1
2
Opening on back
Flue pipe bend