9.0 INFORMATION REGARDING FAULTS
SILOTOP R03
2
FIL.100.--.M.EN Issue: A2
06.12
52
Electronic control panel
No.
Problem
Solution
1
Not working
A) if the MS green LED does not flash
1) Check the power supply on terminal S1
2) Check the performance of the fuse (for replacement, use a fuse of the
same type and having the same value)
B) if the MS green LED flashes
1) Check if there is any enabling signal (verify if the contact S2 is closed)
(CLEAN red LED On)
2) The control panel works properly when there is a power supply of
24 VAC on each pair of EV terminals (See- wiring diagram)