5.0 INSTALLATION AND FIXING
SILOTOP R03
2
FIL.100.--.M.EN Issue: A2
06.12
38
5.8 Pneumatic connections
Compressed air requirements
The operation of the filter requires permanent connection to a compressed air circuit. The compressed air must
be:
1) Clean
- Free of waste which could damage the filter solenoid valves
2) De-humidified
-
The filter tank is provided with a condensation drainage cap. It is recommended to provide
for a condensation separator.
3) Oil-free
- The presence of oily substances in the air could cause premature and irreversibile clogging
Use filters which always keep the air clean and oil-free.
Danger - Warning
Discharge the piping before connecting the compressed air supply to the filter.
Tank inlet pressure
- Minimum 5 bar
- Maximum 6 bar
Variations of the usage conditions may require:
- Modifications of inlet pressure to the tank
- Modifications to the control board settings, that requires changing the compressed air consumptions.
It is recommended to install a Kit (pressure gauge, relief valve) near the filter. A manual cut-off device (ball
valve or similar device) must be inserted on the line to facilitate subsequent maintenance operations.
Important
The filter must be supplied with a separate branch that can be disconnected independently.