200 Service
Touch Panel Standard Line
762-4xxx TP 600
Manual
Version 1.3.0
11.5 Factory Reset
Do not switch the controller off!
The controller can be damaged by interrupting the factory reset process.
Do not switch the controller off during the factory reset process, and do not
disconnect the power supply!
All parameters and passwords are overwritten!
All controller parameters and passwords are overwritten by a factory reset.
Stored boot projects are deleted, including existing web visualization data.
Subsequently installed firmware functions are not overwritten.
If you have any questions, contact WAGO Support.
The controller is restarted after the factory reset.
Proceed as follows to factory reset the controller:
1.
Press the button “CFG/RST.
2.
Set the mode selector switch to the “RESET” position.
3.
Press and hold both buttons until the “SYS” LED alternately flashes
red/green after approx. 8 seconds.
4.
When the “SYS” LED flashes red/green alternately, release the mode
selector switch and the button “CFG/RST”.
Do not interrupt the reset process!
If you release the button “CFG/RST” too early, then the controller restarts without
performing the factory reset.
Содержание Standard TP 600 762-4 Series
Страница 1: ...Manual Touch Panel Standard Line 762 4xxx xxxx xxxx TP 600 WAGO Touch Panel Version 1 3 0...
Страница 69: ...Touch Panel Standard Line Functions 69 762 4xxx TP 600 Manual Version 1 3 0 5 10 Booting Start Behavior...
Страница 70: ...70 Functions Touch Panel Standard Line 762 4xxx TP 600 Manual Version 1 3 0 Browser...
Страница 211: ...Touch Panel Standard Line 211 762 4xxx TP 600 Manual Version 1 3 0...