96
• Feldbus Coupler/Controller
Fieldbus Controller 750-806
WAGO-I/O-SYSTEM 750
DeviceNet
In this case, check the entries for class, instance and attribute, the De-
viceNet connection and the configuration.
6.
In the "Description" dialog box, select the "Set Single Attribute" utility and
enter the following values in the "Object Address" dialog boxes:
- "Class":
4
– "Instance": 64 (64 hexadecimal = 100 decimal)
– "Attribute": 2.
7.
Click in the " Data Sent to the device" dialog box and enter the following
values in hexadecimal:
10 00 06 00 20 A6 24 01 30 01
10 00 06 00 20 A6 24 02 30 01
The path is described by:
0x20 CC (Class) 0x24 II (Instance) 0x30 AA (Attribute)
8.
Click on the "Execute" button to define the mapping.
If the mapping was successful, the fieldbus node sends a “performance”
confirmation.
If a fault has occurred, you will receive a fault message.
In the event of a communication or reply fault, check the DeviceNet con-
nection and whether or not the instance was correctly set.