132
• DeviceNet
Configuration / Parametering with the Object Model
WAGO-I/O-SYSTEM 750
DeviceNet
Description of the instances:
Instance ID
Description
1
reference to the first analog output point
2
reference to the next analog output point
...
255
reference to the last possible analog output point
Instance 1 to 255:
Attribute
ID
Used in
buscoupler
Access
rule
Name
Data type
Description
Value
1
dep. on kind
of connected
modules
get
AOPOBJ_
VALUE
Array of
Byte
output data
actual
output
value
2
dep. on kind
of connected
modules
get
AOPOBJ_
VALUE
USINT
output data length
number
of Bytes
Services:
Service Code
Service Name
Description
0x0E
Get_Attribute_Single
Used to read a DeviceNet Object attribute
value
0x10
Set_Attribute_Single
Used to modify a DeviceNet object attribute
value
5.6.2.2 Supplement to the Object Model for Controller 750-806
5.6.2.2.1 Bit-Strobe
•
Consumed Path changeable (Discrete Output Point (class 0x66) or 0 valid)
•
Produced-Path changeable like a poll connection (if data size more than 8
bytes, only the first 8 bytes are transmitted)
5.6.2.2.2 Dynamic Assembly
•
Two dynamic assembly instances possible (instance 100 and 101)
Attribute ID
Used in
buscoupler
Acces
Rule
Name
DeviceNet data
type
Description of attribute
Semantics
of values
1
Required
Get
Number of
Members in
List
UINT
Max.51 members possible
2
Get/Set
Member List
Array of Struct The member list is an array
of DeviceNet paths
Member Data
Description
UINT
Size of member data
Size in
bits
Member Path
Size
UINT
Size of member path
Size in
bytes
Required
Member Path
(**)
EPATH
3
Required
Get/Set
Data
Array of Byte