• Feldbus Coupler/Controller
Fieldbus Controller 750-806
WAGO-I/O-SYSTEM 750
DeviceNet
3.2.10.1.1 Node
Status
LED
Color
Meaning
IO
red /green
/ orange
The 'I/O' LED indicates the node operation and signals faults occur-
ring.
The Controller starts after switching on the supply voltage. The "I/O" LED
flashes red. Following an error free start up the "I/O" LED changes to green
steady light.
In the case of a fault the "I/O" LED continues blinking red. The fault is cycli-
cally displayed with the blink code.
“I/O”-LED an
Versorgungsspannung
einschalten
Koppler-Hochlauf
“I/O”-LED blinkt
Feldbusstart
Ja
Fehler
Nein
“I/O”-LED
1. Blinksequenz
(leitet opt. Anzeige eines Fehlers ein)
1. Pause
“I/O”-LED
2. Blinksequenz
Fehlercode
(Anzahl Blinkimpulse)
2. Pause
“I/O”-LED
3. Blinksequenz
Fehlerargument
(Anz. Blinkimp.)
Fig. 3-35: Signalling the LED's node status
g012111d
After overcoming a fault, restart the Controller by cycling the power.
I/O
Meaning
green
Data cycle on the internal bus
off
No data cycle on the internal bus
red
Coupler hardware defective
red
blinks
When starting: internal bus is initialized
During operation: general internal bus fault
red
blinks cyclically
Fault message during internal bus reset and internal fault:
orange
MAC-ID is changed via SW and is different to the DIP switch setting