88
• Feldbus Coupler/Controller
Fieldbus Controller 750-806
WAGO-I/O-SYSTEM 750
DeviceNet
DIP switches 7 and 8 are used to set the desired baud rate.
Baud rate
DIP7
DIP8
125 kBaud
*)
OFF
OFF
250 kBaud
ON
OFF
500 kBaud
OFF
ON
not allowed
ON
ON
12
34
5
ON
67
8
1
2
3
4
5
6
7
8
ON
g012541x
Fig. 3-31: Example: Setting the baud
rate 250 kBaud (DIP 7 = ON) of the
station with MAC ID 1.
*)
Presetting
2.
Then switch on the Controller supply voltage.
3.2.9.3 Configuration with Static and Dynamic Assembly
In this example, the software RSNetWorx Rev:3.00.00 of Allan-Bradley and
SLC500 with a 1747-SDN Scanner Module is used.
The inputs are mapped using the static Assembly and the outputs are mapped
with the dynamic Assembly.
The node in the example consists of the following I/O modules:
750-806
402
DI DI
DI DI DODO
402
516
516
516
467
550
600
1
2
3
4
5
6
7
8
DODO DODO AI AI AO AO
Fig. 3-32: Example for a fieldbus node
g012553x
1. Starting Software and EDS file load
1.
Start the configuration software RSNetWorx.
2.
Load the EDS file "750-806_1.EDS" for the fieldbus Controller in
RSNetWorx.
For this click on "Tools/ EDS Wizard" and choose the EDS-file to load.
Note
You can download the EDS file 750-806_1.EDS from the Internet under:
www.wago.com
3.
Now follow the Wizard instructions.