40 IO-Link Interface
787-1668/0000-0080 Electronic Circuit Breaker
Manual
Version 1.1.0, valid from firmware 2.4.0
Table 25: Byte 3 – Validation Bits
Description
Byte 3
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Validation bit 1 (byte 3)
1
0
0
0
0
0
0
0
1
Validation bit 2 (byte 4)
1
0
0
0
0
0
0
1
0
Validation bit 3 (byte 5)
1
0
0
0
0
0
1
0
0
Validation bit 4 (reserved)
0
0
0
0
1
0
0
0
Validation bit 5 (reserved)
0
0
0
1
0
0
0
0
Validation bit 6 (reserved)
0
0
1
0
0
0
0
0
Validation bit 7 (reserved)
0
1
0
0
0
0
0
0
Validation bit 8 (Switching Status)
2
1
0
0
0
0
0
0
0
1
The respective bit (0, 1, 2) must be set to apply the setting from byte 2 (output data) for the
respective send byte.
2
There must be a rising edge on this bit to apply the settings from byte 1 (output data).
Table 26: Possible Combinations for the Optional Process Data
Byte 2
Byte 3
Byte 4
Byte 5
Binary
value
Decimal
value
Optional process data
'0000.0000' 0
–
'0000.0001' 1
Warning overload
(>100 %)
Tripped
Switched OFF local
'0000.0010' 2
Warning 90 % load
Warning overload
(>100%)
Tripped
'0000.0011' 3
Warning 90 % load
Tripped hardware
error
Input voltage
'0000.0100' 4
Warning overload
(>100 %)
Switched ON
Input voltage
'0000.0101' 5
Tripped
Switched ON
Input voltage
'0000.0110' 6
Switched OFF local
Switched OFF remote Tripped
'0000.0111' 7
Switched OFF remote Tripped
Warning 90 % load
'0000.1000' 8
Tripped
Actual current ch1
Actual current ch2
'0000.1001' 9
Tripped
Actual current ch3
Actual current ch4
'0000.1010' 10
Tripped
Actual current ch5
Actual current ch6
'0000.1011' 11
Tripped
Actual current ch7
Actual current ch8
'0000.1100' 12
Switched ON
Tripped
Switched OFF local
'0000.1101' 13
Switched ON
Actual current ch1
Actual current ch2
'0000.1110' 14
Switched ON
Actual current ch3
Actual current ch4
'0000.1111' 15
Switched ON
Actual current ch5
Actual current ch6
'0001.0000' 16
Switched ON
Actual current ch7
Actual current ch8
'0001.0001' 17
Switched ON
Tripped thermal
release
Switched OFF local
'0001.0010' 18
Switched ON
Breaker current ch1
Breaker current ch2
'0001.0011' 19
Switched ON
Breaker current ch3
Breaker current ch4
'0001.0100' 20
Switched ON
Breaker current ch5
Breaker current ch6
'0001.0101' 21
Switched ON
Breaker current ch7
Breaker current ch8
'0001.0110' 22
Switched ON
Breaker RC Status
Input voltage
'0001.0111' 23
Tripped
Breaker current ch1
Breaker current ch2
'0001.1000' 24
Tripped
Breaker current ch3
Breaker current ch4
'0001.1001' 25
Tripped
Breaker current ch5
Breaker current ch6
'0001.1010' 26
Tripped
Breaker current ch7
Breaker current ch8