IO-Link Interface 37
787-1668/0000-0080 Electronic Circuit Breaker
Manual
Version 1.1.0, valid from firmware 2.4.0
Table 21: Bytes 3 … 5 – Configurable Data
Description
Byte 3 … 5
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Status bits when selecting
status messages (e.g.,
“Tripped”)
Channel 1
0
0
0
0
0
0
0
1
Channel 2
0
0
0
0
0
0
1
0
Channel 3
0
0
0
0
0
1
0
0
Channel 4
0
0
0
0
1
0
0
0
Channel 5
0
0
0
1
0
0
0
0
Channel 6
0
0
1
0
0
0
0
0
Channel 7
0
1
0
0
0
0
0
0
Channel 8
1
0
0
0
0
0
0
0
Table 22: Bytes 3 … 5 – Configurable Data when Selecting an Analog Value
Description
Byte 3 … 5
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Analog value when selecting
“Current_chx” or “Input voltage”
0
0
0
0
0
0
0
1
Input Voltage:
The value is displayed with the factor 10 and an offset of 15 V (10 × 15 = 150).
Example: The value 90 corresponds to 24 V (10 × 24 - 150).
Current_chx:
The value is displayed with a factor 10 (value 10 = 1 A).
Below approx. 300 mA, the current measurement becomes inaccurate, so that sometimes 0 A can be displayed.