Device Description 23
787-1668/0000-0080 Electronic Circuit Breaker
Manual
Version 1.1.0, valid from firmware 2.4.0
3.5.3
Technical Data for “Output"
Table 13: Technical Data for “Output"
Nominal output voltage
8 × 24 VDC
Trip current
(can be set via IO-Link interface)
1 A, 2 A, 3 A, 4 A, 6 A, 8 A, 10 A
Trip current
(can be set via rotary switch)
1 A, 2 A, 4 A, 6 A, 10 A
Voltage drop between input and output 200 mV with maximum output current
Device initialization time
250 ms
Wait time after a channel has tripped
(temperature returns to normal)
500 ms (short circuit), 20 s (overload)
Total power dissipation for
output current 8 × 10 A
20 W
Efficiency
99 %
Maximum load capacity per channel
≥
50 mF … 500 mF
Integrated fusing per channel
15 A, slow
ON delay
Based on load:
minimum 50 ms, maximum 5 s
Configurable:
Status query via channel 8,
Status “tripped”
24 V “active low”
Recovery stability
Maximum 35 V
Parallel connection of output channels Prohibited
Series connection of output channels
Prohibited
Output connectors
WAGO-
MULTI CONNECTION
SYSTEM
(
MCS
), 721 Series
Connection: 0.08 mm² … 2.5 mm²
(maximum 1.5 mm² with insulated
ferrule)