Process Image
WAGO-SPEEDWAY 767
767-5803/000-800 8DIO 24V DC 0.5A IF (8xM12)
Manual
Version 1.1.0
8.3
DIO Mode
8.3.1
Input Data
The image for the process data, which are transmitted from the I/O module to the
fieldbus coupler, has a size of 1 byte. If you configure synchronous diagnostic
data for the I/O module, the process image has a size of 3 bytes.
The byte configuration is as follows:
Table 42: DIO input data in the process image
Byte 0 7
0
Digital inputs (process data)
\
-----------------
\/
-----------------
/
1
B
: Input value = True
State of the outputs is also displayed!
Byte 1 7
0
Diagnostic message
| | | | | | | |
| | | | | | | 1
B
: Overtemperature on channel 1
| | | | | | 1
B
: Overtemperature on channel 2
| | | | | 1
B
: Overtemperature on channel 3
| | | | 1
B
: Overtemperature on channel 4
| | | 1
B
: Overtemperature on channel 5
| | 1
B
: Overtemperature on channel 6
| 1
B
: Overtemperature on channel 7
1
B
: Overtemperature on channel 8
Byte 2
7
0
Diagnostic message
\
--------
\/
--------
/
| | | |
|
| | | 1
B
: Short circuit/overload field supply
|
| | always 0
|
| 1
B
: Undervoltage U
LS
|
1
B
: Undervoltage U
A
Not assigned: always 0