WAGO-SPEEDWAY 767
Counter Function
81
767-5803/000-800 8DIO 24V DC 0.5A IF (8xM12)
Manual
Version 1.1.0
9.1
Control of the Counter via Inputs and Outputs
The counter functions (counter) are assigned the sensor and actuator connections
(X1 … X4) as follows:
•
Counter 1
connections X1, X2 (channels 1 … 4)
•
Counter 2
connections X3, X4 (channels 5 … 8)
The assignment of the counter functions to the individual channels is defined in
the following table. By default, the functions "gate input," "count direction input,"
and "switching output" are deactivated via the inputs and outputs. They then
control the counter via the process data (see section "Control and Monitoring of
the Counter via the Process Data").
In order to control the counter functions via the inputs and outputs of the module,
switch these on via DTMs using WAGOframe or another FDT/DTM framework
application. You can find the necessary DTMs at wago.com. This configuration is
also possible with some fieldbus systems (e.g. PROFIBUS
GSD).
Table 48: Connection assignment for the counter function
Inputs and outputs
Connector Description
Counter 1: impulse input
X1
Counter input
Counter 1: gate input
X2
Release input:
0: Counter is blocked. Impulses will
not be counted.
1: Counter is released. Impulses will
be counted.
Counter 1: count direction
input
X3
0: Counter counts up.
1: Counter counts downwards.
Counter 1: switching output
X4
Counts up:
On reaching the set limit value, the
output is set.
Counts down:
On exceeding the limit value 0, the
output is set.
Counter 2: impulse input
X5
See counter 1
Counter 2: gate input
X6
Counter 2: count direction
X7
Counter 2: switching output
X8
For detailed information about connection assignment, see section "Connect
Sensor/Actuator Cable".