WAGO-SPEEDWAY 767
Parameterizing
57
767-5803/000-800 8DIO 24V DC 0.5A IF (8xM12)
Manual
Version 1.1.0
Pos: 30.9 /Serie 767 (WAGO-SPEED WAY)/Par ametrieren/I/O-M odule/Parametri erung 767- 4801, - 02, -05, -06, 58xx, 7401 Globale Diagnosen @ 7\mod_1265877071562_21.docx @ 50302 @ @ 1
Table 30: Information about existing module diagnostics
Global Diagnostics
Diagnostics
Description
Low voltage of U
LS
Disabling the outputs.
If there is an undervoltage of U
A
and/or U
LS
, the
module outputs are disabled. Machine components can
be placed in a dangerous condition, as well as
personnel and machine put in danger.
If an undervoltage of the logic and sensor supply U
LS
of < 18 V occurs
on the module, the outputs are disabled and a corresponding diagnostic
is transmitted to the fieldbus coupler. The F-LED of the module
illuminates.
Low voltage of U
LS
Disabling the outputs.
If there is an undervoltage of U
A
and/or U
LS
, the
module outputs are disabled. Machine components can
be placed in a dangerous condition, as well as
personnel and machine put in danger.
If an undervoltage of the actuator supply U
A
of < 18 V occurs on the
module, the outputs are disabled and a corresponding diagnostic
transmitted to the fieldbus coupler. The module F-LED illuminates.
Pos: 30.10 /Serie 767 ( WAGO-SPEED WAY)/Parametrier en/I/O-Module/Parametrier ung Global e Di agnosen Kurzschl uss/Überlast und U nterbr echung Fel dversorgung @ 8\mod_1278394655719_21.docx @ 59061 @ @ 1
Short circuit/ overload
encoder supply
The module has detected a short circuit or overload of the encoder
supply (only possible when field supply is switched on).
Pos: 30.11 /Serie 767 ( WAGO-SPEED WAY)/Parametrier en/I/O-Module/Parametrier ung Kanaldi agnosen Ü bertemper atur @ 7\mod_1268294869501_21.docx @ 52378 @ @ 1
Table 31: Information about existing channel diagnostics
Channel Diagnostics
Diagnostics
Description
Overtemperature
The module has identified overheating on the corresponding channel
(1 – 8) (only enabled when the actuator output is switched on).
Pos: 30.12 /Serie 767 ( WAGO-SPEED WAY)/Wichtige Erläuter ung en/Sicherheitshinweise/Hinweis/Hi nweis: U nterbrechung S-BU S 48er @ 8\mod_1278393489593_21.docx @ 59044 @ @ 1
Interruption of the S-BUS
If there is an interruption of the S-BUS, the module is automatically put in STOP
mode. The module outputs are disabled.
Pos: 30.13 /D okumentati on allgemei n/Gli ederungsel emente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1