Process Image
WAGO-SPEEDWAY 767
767-5801/000-800 8DIO 24V DC 0.5A IF (8xM8)
Manual
Version 1.1.0
Byte 6 7
0
Diagnostic message
| | | | | | | |
| | | | | | | 1
B
: Overtemperature on channel 1
| | | | | | 1
B
: Overtemperature on channel 2
| | | | | 1
B
: Overtemperature on channel 3
| | | | 1
B
: Overtemperature on channel 4
| | | 1
B
: Overtemperature on channel 5
| | 1
B
: Overtemperature on channel 6
| 1
B
: Overtemperature on channel 7
1
B
: Overtemperature on channel 8
Byte 7
7
0
Diagnostic message
\
--------
\/
--------
/
| | | |
|
| | | 1
B
: Short circuit/overload field supply
|
| | always 0
|
| 1
B
: Undervoltage U
LS
|
1
B
: Undervoltage U
A
Not assigned: always 0
8.5.2
Output Data
The image for the process data, which are transmitted by the fieldbus coupler to
the I/O module, has a size of 4 bytes. If you configure a synchronous diagnostic
confirmation of the I/O module, the process image has a size of 6 bytes.
The process data and the diagnostic confirmation are structured as follows: