WAGO-SPEEDWAY 767
Diagnostics
87
767-5801/000-800 8DIO 24V DC 0.5A IF (8xM8)
Manual
Version 1.1.0
Pos: 43.7 /Serie 767 (WAGO-SPEED WAY)/Di agnose/I/O-Modul e/Betriebsmel dungen 767- 58xx F, I/O (Pos. 16 + 17) @ 7\mod_1268129982669_21.docx @ 52025 @ @ 1
Table 53: Operating messages 2
Pos. LED Color/Status
Cause
Remedy/information
16
F
Red
There is at least one global
diagnostic message on the
module.
Check the supply voltages U
LS
and U
A
of the upstream 767
components. For more
information, see the section
"Parameterizing">
"Diagnostic Overview".
17
I/O
Yellow
Input or output signal
pending.
-
Red*
Error on output.
Check the actuator connection
for short circuit/overload.
A short circuit or overload can
only be diagnosed if the
output is switched on.
* If you set the time of the parameter “Restart delay, actuator” (section
"Parameterizing"> “Parameters of outputs”) to 0 ms, the I/O LED appears yellow
rather than red in case of a short circuit or overload due to the short restart
interval.
Pos: 43.8 /Serie 767 (WAGO-SPEED WAY)/Di agnose/I/O-Modul e/Betriebsmel dungen 767- xxxx U LS und UA (Pos. 18 + 19) @ 8\mod_1278577022948_21.docx @ 59316 @ @ 1
18
U
A
Green
Actuator supply U
A
is
present.
-
Off
Actuator supply U
A
is not
present.
Connect the power supply and
check the voltage level, if
applicable.
19
U
LS
Green
Logic supply and sensor
supply U
LS
are present.
-
Off
Logic supply and sensor
supply U
LS
are not present.
Connect the power supply and
check the voltage level, if
applicable.
Pos: 44 /D okumentation allgemei n/Glieder ungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1