WAGO-SPEEDWAY 767
Parameterizing
59
767-5801/000-800 8DIO 24V DC 0.5A IF (8xM8)
Manual
Version 1.1.0
7.2.2
"DO Module" Mode
Table 33: Overview of adjustable parameters for the digital outputs
Parameter
Description
Function mode
Mode display
Designation
Electronic marking field (max. 40 characters).
Output value
The output state is indicated in this field.
Process image value
This field indicates the value of the output process image for this output.
When manual operation is activated, the field becomes a checkbox.
Activate this checkbox in order to output the state "1" on the output
independently from the control unit.
Signal inverting
Here you can release the current process value as an inverted output
value.
Checkbox unselected*:
Output signal is released as indicated in process image
Checkbox selected:
Output signal is released in an inverted manner as indicated in process
image
Substitute strategy
This releases the substitute value or the last output value in cases such as
a disruption of the fieldbus. You have the following options:
- Switch to substitute value*
- Retain last value**
Substitute value
Enter the process value that is output in case of error. In case of error
(e.g., fieldbus interruption), the value is used with the "Switch to
substitute value" substitute value strategy.
Checkbox unselected:
0
*
Checkbox selected:
1
Manual operation
Activate this checkbox to define the output value independently from the
control unit. When manual operation is activated, the field for the process
image value becomes a checkbox for the manual operation value.
Simulation diagnostics
Activate this check box to switch on the diagnosis simulation. When the
simulation is switched on, the fields for the diagnoses become
checkboxes.