WAGO-TO-PASS® 761
Operation
85
761-214 Telecontrol Module Compact, 8 AI, ESP, DSP
Manual
Version 2.0.0
8.2.1.2
Setting an Analog Output
To set an analog output, send an SMS with the text, which is entered under
Set
output
, and the value to be set to the
TO-PASS
®
telecontrol module. The
TO-
PASS
® telecontrol module acknowledges the command with an SMS containing
the identifier, the transmitted text and the set value.
Example:
Table 41: Example of parameters for
Set AO1
Parameter
Setting
Output Signal
0 ... 20 mA
Min. value
0
Max. value
100
Unit
%
Text
AOUT1=
Send an SMS with the text "AOUT1=75" to set analog output 1 to a value of 15
mA = 75%. The
TO-PASS
®
telecontrol module acknowledges the command with
an SMS containing the identifier and the text "AOUT1=+00075% OK!".
Starting with Firmware 02.33.08, places after the decimal point are also taken into
account for setting of the analog outputs. A period (decimal point) "." must be
used as the separator. Up to four digits are evaluated. For 0 .... 100%, one digit
remains to be used after the decimal point, allowing a value of "75.5" to be
evaluated, for example.
"AOUT1=+075.5%OK!" is transmitted as a reply.