WAGO-TO-PASS® 761
Commissioning
47
761-214 Telecontrol Module Compact, 8 AI, ESP, DSP
Manual
Version 2.0.0
9.
When generating a new configuration file, select the firmware version for
the device that implements the required functionality as the first version in
the
Function selection
field.
The device versions, along with the associated enabling firmware indices
are displayed to make selection easier.
In the field
Module name
enter an identifier for the new device (maximum
8 places for FW version 2.20, or 16 places for all other firmware versions).
This identity is the name of your
TO-PASS
®
telecontrol module and serves
as an identifier. It can only be changed at a later time by completely
overwriting it. The identifier is also transmitted as an SMS, fax or e-mail in
the event of an error and should therefore be a typical identifier that is easy
to associate with the location of use, such as "Tank 1".
10. A new module will be created at the top left of the screen in the project tree.
Click on "+" to reveal the rest of the tree. Select the entry "Identity" and
enter the phone number for the SIM card in the
Phone number
field at the
right. In the following line, deactivate the
[Use PIN]
button, so that the
TO-
PASS
®
telecontrol module does not use the PIN code. Also deactivate the
PIN on the SIM card! To do this, insert the SIM card into a cell phone and
under menu item
Security
select
Deactivate PIN
.
11. If the PIN code must be used, activate the
[Use PIN]
button in the
TO-
PASS
®
operating software and enter the PIN in the field provided. Also
activate the PIN code for your SIM card using your cell phone.
12. Switch on the power to the
TO-PASS
®
telecontrol module. The "Busy" LED
will begin flashing shortly after this.
13. In the operating software select the menu item
Edit > Write parameters
.
The operating software now transmits the parameters to the
TO-PASS
®
telecontrol module.
14. Wait until transmission is complete and the "COM" LED goes out.
15. Switch off the
TO-PASS
®
telecontrol module.
16. Use a pointed object (e.g., screwdriver) to carefully slide the SIM card into
the SIM slot of your
TO-PASS
®
telecontrol module until it locks into place.
The SIM card is then positioned 2 mm within the enclosure.
The SIM card can be released by pressing on it again.
17. Switch the
TO-PASS
®
telecontrol module on again and wait until the
initialization phase is completed. Initialization is completed when the
"Busy" LED goes out.
18. Your
TO-PASS
®
telecontrol module is now ready for use and can be
configured. Follow the instructions given in the Section "Configuration" for
this.