54 Diagnostics
WAGO-I/O-SYSTEM
750
753-647 DALI Multi-Master Module
Manual
Version 1.0.0
The status for the following queries is displayed in the table entries:
Table 20: Diagnostics - Status display for the DALI network in the WAGO-DALI Configurator and
solutions
Table Columns
Explanation
Solution
NA
- N
ot available
Device not available
Check the device, the connection and
the address. If required, re-assign the
address for the device
(see Section "Addressing").
ON
-
Lamp is on
The lamp is switched on Status indication
DF
-
Device fault (error)
Error or failure of device Check the failed device and replace it if
defective. If required, perform data
import using the Replace function
(
[Restore]
function)
(see Section "Configuration").
LD
-
Lamp defect
Lamp is defective
Replace the defective lamp.
LE
-
Limit error
Violation
of
upper/lower
limit
Check the limit settings in the
configuration for the device concerned.
DA
-
Duplicate address
Duplicate
address
detected
To delete duplicate addresses, select the
devices with the identical addresses and
then point to the function
"Delete
selected duplicate addresses"
in the
selection list on the right below the
table.
Then, click the button
[Submit]
.
AM
- Sensor in the active
mode
Sensor is in the active
mode; sensor
transmitting data
Status indication
Operating Hours
Operating Hours
Display of operating hours.
On a device replacement, for example,
you can reset the operating hours to 0.
To do this, select the corresponding
device and point to the function
"Reset
selected operating hours"
in the
selection list on the right below the
table.
Then, click the button
[Submit]
.
You can reset the logged operating hours in the last column of the table to 0 (e.g.,
for replacing a device).
You can replace single, defective devices easily and quickly. The WAGO-DALI
Configurator supports a "Replace" function for this. Using the
[Restore]
button,
the old short address of the previous device is assigned to the new device and the
device settings are then reconstructed using the data stored in the module
database.
Pos: 77 /Dokumentation allgemein/Gliederungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0.doc @ 21810 @ @ 1