WAGO-I/O-SYSTEM 750
Connect Devices
47
753-647 DALI Multi-Master Module
Manual
Version 1.0.0
6.2.2.2
Power Supply Configuration for 787-1007
If power supply is provided using a 787-1007 power supply unit, up to five DALI-
Multi-Master modules can be powered in a fully equipped system (DALI bus
slaves with total power consumption of max. 200 mA).
230 V power supply required!
Note that the 787-1007 power supply unit required 230 V power supply.
Connection of power supply is made at the first DALI Multi-Master module.
Power must be passed on via cable bridges for supply of the other I/O modules.
Abbildung 22: Anschaltprinzip Stromversorgung 787-1007 mit fünf DALI-Multi-Master-
Klemmen
6.2.3
DALI Bus Line
The DALI bus control line consists of one pair of conductors which can be run
together with the 230 V installation.
For example, a 5-conductor cable can be used combining both the voltage supply
and the DALI control line.
The minimum cross section of the conductors depends on the cable length.
Table 18: Conductor cross section depending on the cable length
Cable length
Conductor cross section (min.)
< 100 m
0.5 mm²
100 m – 150 m
0.75 mm²
> 150 m
1.5 mm²
Maximum cable lenght 300 m!
The maximum voltage drop of the DALI line should not exceed 2 V. Therefore,
the maximum cable length between the more distant components is depending on
the conductor cross-section limited to 300 m.