7.4
Data Management Notes
If online access to the devices on the bus is not possible, you can define virtual
DALI devices as an initial step and match these to the actual installation online at
a later time. Offline configuration of the entire DALI network, including control
gear and sensors, can be performed in a limited scope using the WAGO-DALI
Configurator. Device configurations can also be saved and restored, enabling a
replaced device to be reconstructed using the values valid in the database. This
enables you to copy device settings to a different device or to several ones.
7.5
Configuring the DALI Network Using the WAGO-
DALI Configurator (Basic Procedure)
Perform the following steps to configure the DALI-Multi-Master module and the
DALI network linked with the module using the WAGO-DALI Configurator:
1.
Define addresses for the DALI devices
Open the dialog window for addressing the DALI devices using the
[Network]
[Addressing]
buttons in the WAGO-DALI Configurator
toolbar.
2.
Add DALI devices to the tree structure
Before beginning configuration you must add devices from the device list to
the tree structure (left dialog window view) in the configuration window
(right dialog window view) by simple "drag&drop".
Multiple selections are possible.
3.
Configure DALI devices
You can open the dialog window for configuring the DALI devices using
the
[Network]
[Configuration]
button in the WAGO-DALI Configurator
toolbar.
4.
Define DALI groups and scenes
Allocation of the devices to groups and scenes is performed simply by
dragging them to the corresponding group/scene using the mouse.
You can open the dialog window for scene settings using the
[Network]
[Scenes]
button in the WAGO-DALI Configurator toolbar.
You can configure up to 16 standard groups (0 ... 15) and an additional 16
virtual groups (16 ... 31) for 64 devices, with a maximum of 8 devices being
assigned to one virtual group.
5. Perform
diagnosis
Diagnosis of the DALI-Multi-Master module is performed via the
evaluation of the display elements (see Section "Display Elements").
You can perform a diagnosis of the DALI network using the WAGO-DALI
Configurator by clicking the
[Diagnostics]