16
•
750-404 [Up/Down Counter /100 kHz]
Technical
Data
WAGO-I/O-SYSTEM
750
I/O
Modules
2.1.2.6 Technical Data
Module Specific Data
Number of outputs
2
Number of counters
1
Output current
0.5 A short-circuit-protected
Current consumption (internal)
15 mA
Voltage via power jumper contacts
DC 24 V (-15 % ... + 20 %)
Signal voltage
(0): DC –3 V ... +5 V
(1): DC +15 V ... +30 V
Switching rate
max.
100 kHz (750-404, 750-404/000-004)
10 kHz (750-404/000-002)
Input current
typ.
6
mA
Counter depth
32 bits data
Isolation
500 V (System/Supply)
Internal bit width
32 bits data
8 bits control /status
Dimensions W x H* x L
* from upper edge of 35 DIN rail
12 mm x 64 mm x 100 mm
Weight
ca. 55 g
Standards and Regulations (cf. Chapter 2.2 of the Coupler/Controller Manual)
EMC-Immunity to interference (CE) acc. to EN 50082-2 (96)
EMC-Emission of interference (CE) acc. to EN 50081-1 (93)
Approvals (cf. Chapter 2.2 of the Coupler/Controller Manual)
C
UL
US
(UL508)
ABS (American Bureau of Shipping)
BV (Bureau Veritas) (applied for)
DNV (Det Norske Veritas)
Cl. B
GL (Germanischer Lloyd) (applied for)
Cat. A, B, C, D
KR (Korean Register of Shipping)
LR (Lloyd's Register)
Env. 1, 2, 3, 4
NKK (Nippon Kaiji Kyokai)
PRS (Polski Rejestr Statków)
RINA (Registro Italiano Navale)
C
UL
US
(ANSI/ISA 12.12.01)
Class I Div2 ABCD T4