750-404/000-003 [Frequency Counter 0.1 Hz-100 kHz] • 35
Technical Data
WAGO-I/O-SYSTEM 750
I/O Modules
2.1.4.5 Technical Data
Module Specific Data
Number of outputs
2
Number of counters
1
Output current
0.5 A short-circuit-protected
Current consumption
max.
75 mA at DC 5 V
Voltage via power jumper contacts
DC 24 V (-15 % ... + 20 %)
Signal voltage
(0): DC –3 V ... +5 V
(1): DC +15 V ... +30 V
Switching rate
max.
100 kHz
Pulse width
min.
10
µs
Input current
typ.
5 mA
Counter depth
32 Bit
Isolation
500 V (System/Supply)
Internal bit width
32 bits data
8 bits control /status
Dimensions W x H* x L
* from upper edge of 35 DIN rail
12 mm x 64 mm x 100 mm
Weight
ca. 55 g
Maximum frequency range
Integration time = 1 period
0.1 Hz - 8 kHz, resolution 0.001 Hz
Integration time = 4 period
0.25 Hz - 32 kHz, resolution 0.01 Hz
Integration time = 16 period
1 Hz - 100 kHz, resolution 0.1 Hz (1 Hz)
Measuring error at the maximum frequency range
Range 0.1 Hz - 8 kHz
<
1 %
Range 0.25 Hz - 32 kHz
<
1.5 %
Range 1 Hz - 100 kHz
<
1.5 %
Lower frequency range*
Integration time = 1 period
0,1 Hz - 100 Hz, resolution 0.001 Hz
Integration time = 4 period
1 Hz - 1 kHz, resolution 0.01 Hz
Integration time = 16 period
10 Hz - 10 kHz, resolution 0.1 Hz (1 Hz)
Measuring error at the lower frequency range *
Range 0,1 Hz - 100 Hz
<
0.05 %
Range 1 Hz - 1 kHz
<
0.05 %
Range 10 Hz - 10 kHz
<
0.2 %
* For Measurements in a lower frequency range, the measuring error is lower than the
measuring error using the maximum frequency rang.
Standards and Regulations (cf. Chapter 2.2 of the Coupler/Controller Manual)
EMC-Immunity to interference (CE) acc. to EN 50082-2 (96)
EMC-Emission of interference (CE) acc. to EN 50081-1 (93)