38
•
750-404/000-003 [Frequency Counter 0.1 Hz-100 kHz]
Process
Image
WAGO-I/O-SYSTEM
750
I/O
Modules
Input data
Output data
S0
Status byte
C0
Control byte
D0
Frequency value byte 0 (LSB)
D0
Watchdog-time byte 0 (LSB)
D1
Frequency value byte 1
D1
Watchdog-time byte 1 (MSB)
D2
Frequency value byte 2
D2
reserved
D3
Frequency value byte 3 (MSB) D3
reserved
Control byte
B7
B6
B5
B4
B3
B2
B1
B 0
0 0 0
T
VD
REQ
Set
output
DO 2
Set
output
DO 1
RANGE_
SEL
REQ1
RANGE_
SEL
REQ0
T
VD
REQ
Request to change the Watchdog time (T
VD
) with valid data.
RANGE_SEL REQ1
Selection of the integration time and the representation of
measured frequency value.
RANGE_SEL REQ0
Selection of the integration time and the representation of
measured frequency value.
0
This constant must be set to zero.
Status byte
B7
B6
B5
B4
B3
B2
B1
B0
X X
ST_
GATE
T
VD
ACK
Status
output
DO 2
Status
output
DO 1
RANGE_
SEL
ACK1
RANGE_
SEL
ACK0
ST_GATE
Status of the GATE input (0=enabled, 1=disabled)
T
VD
ACK
Acknowledgement T
VD
changed.
RANGE_SEL ACK1 Acknowledgment to Range Selection, Frequency values are valid.
RANGE_SEL ACK0 Acknowledgment to Range Selection, Frequency values are valid.
X
This value is not evaluated.
With the control and status byte the following tasks are possible:
Setting the Method of Measuring, Frequency Range and Representation:
The method of measuring and the representation depends on the
RANGE_SEL REQ bits in the CONTROL byte. Dependent on the adjusted
measuring method also the maximum frequency range changes.
The following table illustrates the different modes.