* Global heartbeat timing
To check, or monitor, whether the slave unit is active or not, use the heartbeat or the node guarding.
50 to 21844ms (default: 200ms)
* NMT inhibit time
This is the setting to inhibit the master unit to send NMT messages continuously.
NMT stands for “Network Management”.
0 to 3276.7ms (default: 5ms)
* On Error Control Event of a mandatory slave
Select from the following 3.
-
Stop all nodes
-
Reset all nodes
-
Treat the slave individually (default)
For WAGO 750-337, use the default because DS302 is not supported.
If you select [Treat the slave individually], each slave unit sends the reset signal, not the master unit
sends the reset signal by broadcast.
5.3.2
Error control overview
The Error Control Overview tab allows you to check the list of the node monitor (Heartbeat / Node guard).
5.3.3
Advanced object configuration
The Advanced Object Configuration tab shows the list of objects of the master unit.