15
* Event timer, Inhibit time
The Event timer and the Inhibit time can be set when the transmission type is set to Asynchronous event.
The Event timer is the setting to send data consistently besides to send it when it changes.
The Inhibit time is the setting to inhibit increase of communication load by continuous data change.
* Identity settings
The master unit makes matching check between the device information (the contents of the imported
EDS file) and the actual slave unit when communication starts.
Items to be checked are follows.
Device type
Vendor ID
Product code
Revision number
[NOTE]
Check off the [Revision number] when connecting with 750-337.
When connecting with WAGO 750-337, the Device type cannot be selected.
The imported EDS file identifies if each item is enabled or disabled.