Wago - 4PU & 4PS - 34
A3.3 Modbus write register
Reg. address
Content
Function code
Length
Unit
Data type
4003
Modbus ID
06
1
-
Signed
Command:
01 06 4003 000A (new ID: 10)
01~247 - 01 default - 00 broadcast
4004
Baud rate
06
1
-
Signed
Command:
01 06 4004 00 06 (new Baudrate: 9600)
1: 300 - 2: 600 - 3: 1200 - 4: 2400
5: 4800 - 6: 9600 - 7: 19200
8: 38400 - 9: 57600 - 10: 115200
400D
S0 output rate
10
2
imp/kWh Float ABCD
Command:
01 10 400D 0002 04 41 20 00 00 (new S0: 10)
10.000 - 2.000 - 1.000 - 100 - 10 - 1 0,1 - 0,01
400F
Combination code
06
1
-
Signed
Command:
01 06 400F 0004 (new code: 4 F-R)
1: forward only - 2: reverse only
3: reverse
4: import-export
5: import-export (10)
4010
LCD cycle time
06
1
sec.
HEX
Command:
01 06 4010 0025 (new time: 25 sec.)
01~30
4011
Parity setting
06
1
-
Signed
Command:
01 06 4011 0002 (new parity: none)
01: even - 02: none - 03: odd
4016
Power down counter
06
1
-
Signed
Command:
01 06 4016 0000
Reset to 0
6048
Tariff
06
1
-
Signed
Command:
01 06 6048 0002 (new tariff: 2)
1: T1 - 2: T2 - 3: T3 - 4: T4
6049
Resettable day counter
10
1
kWh
Float ABCD
Command:
01 10 6049 0002 04 0000 0000
Reset to 0
401F
CT ratio
2
-
Signed
Command:
01 10 401F 0002 04 9995 0005
Set to 9995/5
4021
Pulse width
06
1
ms
Signed
Command:
01 06 4021 0030 (new setting: 30ms)
2~99 ms
4022
Pulse type
06
1
-
Signed
Command:
01 06 4022 0002 (new setting: forward &
reverse)
2 = forward & reverse
4026
Data type setting
06
1
-
Signed
Command:
01 06 4026 0002 (new setting: integer)
1=standard, 2=Integer
4032
Screen direction
06
1
0 -
Signed
Command:
01 06 4032 0001 (new setting: turn 180
degrees)
0: standard - 1: turn 180 degrees
4033
OBIS code ON/OFF
06
1
0 = Signed
Command:
01 06 4033 0001 (new setting: OBIS ON)
0: OFF - 1: ON
Содержание 4PS