Wago - 4PU & 4PS - 17
The default imp/kWh setting for the S0 output is 1.000Imp/kWh. The S0 output setting can be set via push buttons direct on the
meter or via bluetooth app to 10.000 / 2.000 / 1.000 (default) / 100 / 10 / 1 / 0,1 / 0,01 Imp/kWh.
6.6.4 Pulse type setting
The default pulse type setting is active & reactive. This means that the two pulse outputs pulse based on the active and reactive
energy. The pulse type can be set to forward & reverse, which means that the pulse outputs pulse based on forward and reverse
active energy.
6.6.5 S0 Pulse width
The default S0 pulse width is 30ms. The pulse width setting can be modified to 2-99ms (depending on the imp/kWh setting).
6.6.6 Modbus ID
The Modbus ID can be set from 1 to 247, the default Modbus ID is
1.