A2.3 M-Bus write registers
Contents
Command part 1
Address
Command part 2
New value
Response
Remarks
Baudrate
68 03 03 68 53
01
-
BB
E5 (new Baud 2400)
B8 = 300; B9 = 600; BA = 1200; BB = 2400; BC = 4800; BD = 9600
Primary address
68 06 06 68 53
01
51 01 7A
01
E5 (new id 01)
000 - 250 write in HEX
Secondary address
68 09 09 68 53
01
51 0C 79
15 01 23 45 E5 (new address 1501 2345)
4 bytes BCD same as read
Tariff mode
68 08 08 68 53
01
51 09 7C 01 54
02
E5 (tariff 2)
T1 = 01 ; T2 = 02 ; T3 = 03 ; T = 04
Combined code
68 07 07 68 53
01
51 09 FD 3A
05
E5 (combined code 05)
01, 02, 03, 04 and 05
S0 rate
68 0A 0A 68 53
01
51 0C FD 3A
00 00 01 00 E5 (S0 rate 100)
10.000 / 2.000 / 1.000 / 100 / 10 / 1 / 0,1 / 0,01
Resettable kWh
68 09 09 68 53
01
51 0C 04
00 00 00 00 E5
Value is ignored, always set to 0
Reset power down counter
68 08 08 68 53
01
51 0A FD 60
00 00
E5
Value is ignored, always reset to 0
SND NKE
10 40
01
-
-
E5
Can be send to primary or secondary address and resets all communication values
Selecting slave by secondary addressing
Serial number
Manufacturer ID
Generation version
Medium
68 0B 0B 68 53 FD 52
aa aa aa aa
bb bb
cc
dd
Input
01 00 07 13
CD 25
01
02
Remarks
13070001
-
Major version of the software
Electricity
Содержание 4PS