8 - 4PU & 4PS - Wago
4.2 Basic errors
0,05Ib
Cosφ = 1
±1,5%
0,1Ib
Cosφ = 0,5L
±1,5%
Cosφ= 0,8C
±1,5%
0,1Ib - Imax
Cosφ = 1
±1,0%
0,2Ib - Imax
Cosφ = 0,5L
±1,0%
Cosφ = 0,8C
±1,0%
4.3 Bluetooth specification
Protocol
BLE 4.2
Frequency range
Bluetooth 4.0: 2402 - 2480 MHz (40 CH)
4.4 M-bus communication specification
Bus type
2- wire (M-bus)
Baud rate
300, 600, 1200, 2400 (default), 4800 and 9600
Range
1000m
Downlink signal
Master to slave. Voltage modulation
Uplink signal
Slave to master. Current modulation
Cable
JYSTY (nx2x0,8)
Protocol
EN13757-3
Unit loads
1
Max. number of meters
64 per bus*
4.5 Modbus/RS485 communication specification
Bus type
RS485
Protocol
MODBUS RTU with 16 bit CRC
Baud rate
1200, 2400, 4800, 9600 (default), 19200, 38400, 57600 and 115200
Address range
1-247 user settable
Maximum bus load
60 meters per bus*
Range
1000m
*Note that the maximum number of meters is dependent on the converter, baudrate (the higher the baudrate, the smaller the
number of meters which can be used) and the circumstances under which the meters are installed.