7 Troubleshooting
Caution
•
During repair and maintenance, do not touch the meter connecting clamps directly with your bare hands, with
metal, blank wire or other conducting material as that will cause an electric shock and possibly cause injury, serious
injury or even death.
•
Turn off and if possible lock all sources supplying the energy meter and the equipment that is connected to it
before opening the protection cover and working on it.
•
Turn off and lock all power supply to the energy meter and the equipment to which it is installed before opening
•
the protection cover to prevent the hazard of electric shock.
Warning
•
Maintenance or repair should only be performed by qualified personnel familiar with applicable codes and
regulations.
•
Use insulated tools to maintain or repair the meter.
•
Make sure the protection cover is in place after maintenance or repair.
•
The case is sealed, failure to observe this instruction can result in damage to the meter.
Problem
Mögliche Ursache
Überprüfung / Lösung
The red consumption LED is not flashing
(PULSE LED).
There is no load connected to the
meter. The load on the line is very low.
Connect a load to the meter. Check with
an Ohm-meter if the load value is very
low.
The register
doesn’t
count.
There is almost no load connected to the
meter.
Check if the red consumption LED is
flashing.
No pulse output.
The pulse output is not supplied with DC
power. The pulse output is not connected
correctly.
Check the external voltage source (Ui) is
5-27V DC with a voltage meter. Check if
the connection is correct: the 5-27V DC
should be connected to the collector
connection (pin 4/6) and the signal wire
to the emitter connection (pin 5).
If none of the above works, please contact technical support