2789-9023
Fieldbus Description
38
Product manual | Version: 1.0.0
EtherNet/IP Communication Module
Time
Table 42: Internal Module Parameters – Time
Attribute
ID
Access
Data type Description
Value Limits
Factory setting
Min.
Max.
262
Get/Set
UINT8
Hours
0
0
23
Get/Set
UINT8
Minutes
0
0
59
Get/Set
UINT8
Seconds
0
0
59
264
Get/Set
UINT16
Time zone
0
−12
12
265
Get/Set
UINT16
Synchronization mode
(1 = off, 2 = read time
from the lower-level
device, 4 = write time
from module, 8 = up-
date time with SNTP)
1
This object supports the following common services.
Table 43: Common Services
Service
Code
Service Available
Service Name
Description
Class
Instance
0x0E
Yes
Yes
Get_Attribute_Single
Returns the content of the respective attribute
0x10
No
Yes
Set_Attribute_Single
Modifies an attribute value
4.2.9 Measurement Data Object
The Measurement Data object (Class 0x8C) allows the events and measured values of a
lower-level device to be read. Only instance ID 1 is implemented for this object.
4.2.9.1 Events and Measured Values
The object outputs the WAGO-specific events and measured values listed below.
Process Output Data
Table 44: Events and Measured Values – Process Input Data
Attribute ID
Access
Data type
Description
0
Get
UINT16
Output voltage (unit: mV)
1
Get
UINT16
Output current (unit: mA)