2789-9023
Fieldbus Description
Product manual | Version: 1.0.0
25
EtherNet/IP Communication Module
4.2.2.1 Instances
Assembly instance 101 (attribute ID 3) contains the process input data.
Table 18: Assembly Object – Instance 101, Attribute ID 3
No.
Access
Name
Data type
Description
1
Get
EtherNet/IP module
status
UINT16
Bit 0
Communication with lower-
level device OK
Bits 1 … 15
Reserved
2
Get
Output voltage (mV)
UINT16
3
Get
Output current (mA)
UINT16
4
Get
Status
UINT16
Bit 0
DC status OK
Bit 1
Overheating status
Bit 2
No output voltage
Bit 3
Output, short circuit
Bit 4
Digital input status
Bits 5 … 15
Reserved
5
Get
Warnings
UINT16
Bit 0
Output, undervoltage
Bit 1
Output, overvoltage
Bit 2
Overload
Bit 3
Adjustable output current limit
exceeded
Bit 4
Adjustable operating hours
limit exceeded
Bit 5
TopBoost supplied
Bit 6
PowerBoost supplied
Bit 7
High device temperature
Bits 8 … 15
Reserved
6
Get
Error
UINT16
Bit 0
Overheating, device switched
off
Bit 1
No output voltage
Bit 2
Output short circuit
Bit 3
Electronic circuit breaker
tripped
Assembly Instance 102 contains process output data.
Table 19: Assembly Object – Instance 102
Attribute ID Access
Name
Data type
Description
3
Get/Set
Control word
UINT16
Bit 0
Device standby (not
supported)
Bit 1
Digital output on
Bits 2 … 15
Reserved
The software inspects the writing of attribute 3 of Assembly instance 102. If the limit value
has been exceeded, it is identified and, if necessary, corrected. However, a write request
is not rejected.
Assembly instance 103 is provided as a configuration object for implicit communication.
The object is not used and returns no data when read out.