Technical Manual
WDGA with EtherNet/IP
6 - Commissioning
© Wachendorff Automation GmbH & Co. KG
51
A window opens again in which you can select the name, the IP address, the
description (optional), and the assemblies. You can find out which assembly is suitable
for you from the tables in 4.3.
Figure 6.17: General
If you click on "Change ..." in the "General" window, you can set the assembly
accordingly. In this chapter we will only work with Assembly 1 for the time being. We
recommend to select DINT for "Size", so that you receive the position value as 32-bit
block.
Figure 6.18: Choose assembly
Under the "Connection" tab you can now set the cycle time (RPI) and the "Connection
over EtherNet/IP". Now click on "OK". The encoder should now be displayed in the left
column of the project navigation.