Vysa-Therm™ 3000: 000807
Vysal Limited. Unit 3 Lovett Farm, Little Somerford, Wiltshire, SN15 5BP. Tel : 01666 822059 Fax: 01666 822422
Email: [email protected] Web: www.floor-heating.co.uk
2. Factory default settings
2.1 DIL switches
SW1: on=28°C (wooden floor)
SW2: off=room sensor operation disabled
SW3: on=floor sensor operation enabled
SW4: on=timed operation
2.2 Program Times.
Default is timed operation (from DIL switch)
Default day mode is 5:2
Program mode is d 5:2 and any of these periods, times or temperature settings can be changed or deleted very easily as required
2.2.1 Weekday times.
All days in 1 day mode; Weekdays in 5:2 day mode; Mo, Tu, We, Th and Fr in 7 day mode
Timer period 1, comfort temperature, starts 06:00
Timer period 2, savings temperature, starts 08:00
Timer period 3, comfort temperature, starts 16:00
Timer period 4, savings temperature, starts 22:30
2.2.2 Weekend times.
Weekend days in 5:2 day mode; Sa and Su in 7 day mode
Timer period 1, comfort temperature, starts 08:00
Timer period 2, savings temperature, starts 12:00
Timer period 3, comfort temperature, starts 12:00
Timer period 4, savings temperature, starts 23:00
2.3 Temperatures.
Default sensor mode is floor sensor only control (from DIL switches).
Default temperature display mode is °C.
Frost temperature is fixed as 5°C, this is the floor or air temperature.
Savings temperature, floor sensor only mode, 20°C floor temperature
Savings temperature, floor and room sensor/room sensor only mode, 15°C air temperature
Comfort temperature, floor sensor only mode, 26°C floor temperature
Comfort temperature, floor and room sensor/room sensor only mode, 21°C air temperature
3. Software features
3.1 Mode of operation.
There are two modes of operation; timed or un-timed. The mode is initially selected by DIL switch during installation but can be changed later under the
configuration menu without having to open the control.
When
timed operation is chosen the control uses a real time clock and timer periods to change the temperature between the comfort temperature and the
savings temperature.
When
un-timed operation is chosen the control is set to the required temperature using
S
and
T
and controls to this temperature until it is adjusted.