9. Electrical and electronic specifications.
Supply Voltage: 230 Vac nominal (operating range 200 to 260 Vac), 50/60 Hz
Standby power consumption: 500 mW
Relay rating: 16 A resistive (4 A inductive), 230 Vac, 3600 W
Ambient operating temperature: 0 to 35 °C
Room sensor control set point range: 5 to 35 °C
Room sensor display and setting resolution: 0.2 °C
Room sensor operating differential: 0.4 °C
Room sensor accuracy: ± 1.5 °C over range 10 to 30 °C
Room sensor: built in NTC thermistor
Floor sensor control set point range: 5 to 45 °C
Floor sensor display and setting resolution: 0.2 °C
Floor sensor operating differential: 1.0 °C
Floor sensor accuracy: ± 2.0 °C over range 10 to 40 °C
Floor sensor: NTC thermistor, resistance 10k
Ω
@25 °C
Floor sensor: the length of the floor sensor lead can be extended up to a maximum of 20 m.
Clock: crystal controlled with time and date plus automatic summer time correction
Clock accuracy: ± 25 PPM (parts per million)
Clock battery backup: replaceable lithium coin cell (Type CR2032)
Timer program, settings and configuration stored in non volatile EEPROM memory
Connections: 7 by 4.0 mm² rising clamp screw terminal
(Live in, Neutral in, Live to load, Neutral to load, Earth - no internal connection, floor sensor signal, floor sensor return)
Keypad buttons: 6 silicon rubber (
S
,
T
, OK, MENU, 24h, O/I)
LCD: custom, 16mm x 30mm, 60 segment, reflective (no backlight) - see appendix.
DIL switch setting of operating modes by installer
Switch 1, floor sensor maximum temperature select: on=28°C (wood floor), off=35°C (tiled floor)
Switch 2, room sensor operation select: on=use room sensor, off=do not use room sensor
Switch 3, floor sensor operation select: on=use floor sensor, off=do not use floor sensor
Switch 4, timed operation select: on=timed operation, off=un-timed operation
The wiring requirements for the Vysa-Therm™ 3000 are printed on the reverse of the thermostat above the terminal connections.
The floor sensor and the cold tail leads must not be placed in the same conduit.
If the heating load exceeds the thermostats 16A switching capacity then the heating will be required to be connected via a contactor of sufficient rating. In this
case terminal 4 becomes the live terminal to switch the contactors coil.
Rear of the thermostat showing the identification markings.
1 2 3 4
6
5 7
Mains input
230 V ~ 50 Hz
Heating
Load
Floor Sensor
10K
Ω
NTC
Thermistor
Maximum load: resistive 16 A
www.floor-heating.co.uk
Vysa-Therm™ 3000
Earth
N
L
L
N
IP 31
T 35
VYSAL
®