background image

8  

VST5000W5028W

 Wireless Survey Tools User Guide 

Orphan Nodes

It is important to understand that if a network is started 
up incorrectly it “may” result in orphaned or unassigned 
devices / nodes / controllers that will NOT join the ZigBee 
network. Let’s fi rst understand how an orphan node is 
created. A typical example is when jobs are started on 
a technician desk before sending the devices / nodes 
/ controllers to the fi eld for installation. Often the 
integration technician will begin by powering up the 
Jace – coordinator and connect it to the Workbench tool 
creating and adding the Wireless Tstat Network driver 
layer.

Once the Wireless Tstat Network driver layer is up and 
running, the technician will then open and start up the 
wireless devices / nodes / controllers one by one and add 
them to their Niagara database. 

•  They will power the fi rst unit, then add it to the 

database  and fi nally power it down.

•  They will power up the second unit, add it to the 

database and then power it down.

•  This will be repeated to a maximum of 6 devices.

This will work fi ne for the fi rst 6 devices only, simply 
because the Jace – coordinator  can provide a maximum 
of 6 assignable addresses. When the technician powers 
up the 7th device / node / controller, it will NOT be able 
to join the ZigBee network unless one of the previous 
device / node / controller is powered back on. Once this 
is done, it will be able to assign the next 6 addresses as 
usual.

In order to add another 6 devices, one of the previously 
added device needs to be left on. If 42 devices are to 
be added to the network, 8 of them should ALWAYS be 
powered and be within connectivity range of all the 
others.

How would orphan nodes appear in the fi eld and how 
would you allow them to join the ZigBee network ? 

Knowing and understanding 

the 6A / 

5H

  rule of ZigBee

VYKONStat Wireless Networks are based on, a standard 
which is suitable for wireless sensor and controller 
networks. In ZigBee, a device / node / controller is said to 
join a network if it can obtain a ZigBee network address 
from a parent device. This ZigBee address is a value which 
is NOT initially exposed or available for the integrator to 
see.

Devices / nodes / controllers can calculate and assign 
addresses for their surrounding devices by a distributed 
address assignment scheme. This assignment is fl exible, 
but it does somewhat restricts the number of attached 
devices and the possible depth of the said network for 
any given device on the network. 

ZigBee supports three kinds of networks type: star, 
tree, and mesh networks. The ZigBee coordinator ( In 
our case, this is the VWG ) is responsible for initializing, 
maintaining, and controlling the network. 

•  A star network has a coordinator with devices 

directly connecting to the coordinator. 

•  A tree and mesh networks, devices can communicate 

with each other in a multi-hop fashion. 

The network is formed by one ZigBee coordinator and 
multiple ZigBee routers. A device can join a network as 
an end device by the associating with the coordinator or 
a router.

A ZigBee device / node / controller is said to have 
successfully joined a network if it can obtain a ZigBee 
network address from the main Jace coordinator or any 
other router devices / nodes / controller. 

6A stands for 6 addresses maximum 

per device / node / controller 

Any given device / node / controller including the 
Jace –coordinator can ONLY give a maximum 6 ZigBee 
addresses out to other devices so they join the active 
ZigBee network. This means for any device / node 
/ controller to be able to successfully join a ZigBee 
network, it needs an address to be assigned by another 
device / node / controller which is within connectivity 
and that has NOT already assigned its maximum of 6 
addresses allowed.

Please note that once a device / node / controller has 
been assigned a ZigBee address & has joined the active 

ZigBee network, it will save its assigned ZigBee address 
to fl ash memory & re-use it afterwards even after a power 
failure or a network re-start. The ONLY time device / node 
/ controller would require a NEW ZigBee address is if the 
network is re-started with either a new PAN ID or a new 
Channel value. This causes the currently assigned & saved 
ZigBee address in fl ash to be erased & will force the / 
node / controller to try to re-join a new network.

Содержание VST5000W5028W

Страница 1: ...VST5000W5028W Wireless Survey Tools User Guide August 30th 2010...

Страница 2: ...nal Strength Indicator Please note that it is normal for the value to fluctuate slightly up to 10 20 The final reading value is representative of the median averaged values displayed Any value from 10...

Страница 3: ...plications such as going through stair ways but the design and optimization of the thermostat antenna is designed for optimal horizontal distance penetration and not a vertical one As such be prepared...

Страница 4: ...at at least one thermostat is within 50 feet 15 M of the VWG for every cluster of 10 thermostats installed Always install the VWG closest to the center of all associated wireless thermostats Always lo...

Страница 5: ...installed If possible perform the survey during occupied hours where other electronic devices such as computers wireless laptop cell phones PDA s wireless telephones microwave ovens light ballasts etc...

Страница 6: ...ge radius of the coordinator VWG or Jace Driver at it s proposed location It s possible that another location may improve your network performance or that you may require an additional coordinator VWG...

Страница 7: ...t t Fig 11 5 Then find the potential coverage radiuses through a few of the thermostats furthest away from the coordinator VWG or Jace Driver covered radius fig 10 6 Once the most difficult connectivi...

Страница 8: ...from a parent device This ZigBee address is a value which is NOT initially exposed or available for the integrator to see Devices nodes controllers can calculate and assign addresses for their surrou...

Страница 9: ...te ZigBee addresses to the other devices in building B Within Range Jac t t t t t t t t t t t t t t Jace Building A Building B Fig 12 5H stands for 5 hops maximum ANY given device node controller shou...

Страница 10: ...and will force the node controller to try to re join a A A B B A B Jace Coordinator Proposed location Maximum linear distance covered by a single Jace Coordinator 20 20 20 20 20 Fig 14 5 Leave survey...

Страница 11: ...the information contained therein is solely at the risk of the user Documentation may include technical or other inaccuracies or typographical errors Vykon reserves the right to make changes to this...

Страница 12: ...VYKON 3951 Westerre Parkway Suite 350 I Richmond VA 23233 I USA Phone 804 747 4771 I Fax 804 747 5204 contact tridium com I www vykon com 028 0318 R0...

Отзывы: