background image

2  

VST5000W5028W

 Wireless Survey Tools User Guide 

Index

Product Overview

  2

VYKONStat Wireless Network Overview 

   2

 

Basic Initial Design And 
Deployment Consideration 

  3

Site Survey Overview  

  5

Knowing and understanding 
the 6A / 5H  rule of ZigBee  

  8

6A stands for 6 addresses maximum 
per device / node / controller  

  8

Orphan Nodes 

  8

5H stands for 5 hops maximum 

  9

Best practice VYKONStat Wireless initial 
network start-up procedure 

 10

Disclaimer 

 11

SUR-A-5000 & SUR-B-5000

Product Overview    

 

The Vykon wireless survey tools are intended to verify 
and validate the deployment and use of the Vykon 
wireless thermostats on a potential job site.

Included in this package you will fi nd the following items: 
 

  •  2 x Survey devices: SUR-A-5000 & SUR-B-5000
  •  2 x 120 Vac charger for the tools

Before performing a survey, please insure that 
both survey tools are fully charged overnight.

The survey tool will display a numerical percentage 
value on the LCD screen which represents the wireless 
network ZigBee RSSI dBi value (Receiving Signal Strength 
Indicator). 

Please note that it is normal for the value to 
fl uctuate slightly (up to 10-20%). The fi nal 
reading value is representative of the median 
averaged values displayed. 

  •  Any value from 10 to 100% indicates good    
   VYKONStat 

Wireless 

connectivity.

  •  Any value below 10% “may” indicate that  

 

    an extra Router VRP5000W1000W  may need to  
   be 

installed.

VYKONStat Wireless Network Overview 

 

 

 

VYKONStat Wirelessis a specifi cation for a suite of high 
level communication protocols using small, low-power 
digital radios based on the IEEE 802.15.4-2003 standard 
for wireless personal area networks (WPANs).

Mesh networking is a type of network where each node 
in acts as an independent router. It allows for continuous 
connections and reconfi guration around broken or 
blocked paths by “hopping” and “re-meshing” from node 
to node until the fi nal destination is reached. 

General characteristics of the wireless physical 
communication layer are:

•  Uses a wireless physical layer of 2.4GHz with a data  
  rates of 250 kbps
•  Yields high throughput and low latency
•  Automatic topology confi guration: star,   

 

 peer-to-peer, 

mesh

•  Handshake protocol for transfer reliability
•  Range: 50 feet / 15M typical (up to 100 feet / 30 M  
  based on environment)

Содержание VST5000W5028W

Страница 1: ...VST5000W5028W Wireless Survey Tools User Guide August 30th 2010...

Страница 2: ...nal Strength Indicator Please note that it is normal for the value to fluctuate slightly up to 10 20 The final reading value is representative of the median averaged values displayed Any value from 10...

Страница 3: ...plications such as going through stair ways but the design and optimization of the thermostat antenna is designed for optimal horizontal distance penetration and not a vertical one As such be prepared...

Страница 4: ...at at least one thermostat is within 50 feet 15 M of the VWG for every cluster of 10 thermostats installed Always install the VWG closest to the center of all associated wireless thermostats Always lo...

Страница 5: ...installed If possible perform the survey during occupied hours where other electronic devices such as computers wireless laptop cell phones PDA s wireless telephones microwave ovens light ballasts etc...

Страница 6: ...ge radius of the coordinator VWG or Jace Driver at it s proposed location It s possible that another location may improve your network performance or that you may require an additional coordinator VWG...

Страница 7: ...t t Fig 11 5 Then find the potential coverage radiuses through a few of the thermostats furthest away from the coordinator VWG or Jace Driver covered radius fig 10 6 Once the most difficult connectivi...

Страница 8: ...from a parent device This ZigBee address is a value which is NOT initially exposed or available for the integrator to see Devices nodes controllers can calculate and assign addresses for their surrou...

Страница 9: ...te ZigBee addresses to the other devices in building B Within Range Jac t t t t t t t t t t t t t t Jace Building A Building B Fig 12 5H stands for 5 hops maximum ANY given device node controller shou...

Страница 10: ...and will force the node controller to try to re join a A A B B A B Jace Coordinator Proposed location Maximum linear distance covered by a single Jace Coordinator 20 20 20 20 20 Fig 14 5 Leave survey...

Страница 11: ...the information contained therein is solely at the risk of the user Documentation may include technical or other inaccuracies or typographical errors Vykon reserves the right to make changes to this...

Страница 12: ...VYKON 3951 Westerre Parkway Suite 350 I Richmond VA 23233 I USA Phone 804 747 4771 I Fax 804 747 5204 contact tridium com I www vykon com 028 0318 R0...

Отзывы: