background image

10  

VST5000W5028W

 Wireless Survey Tools User Guide 

Best practice VYKONStat Wireless initial 

network start-up procedure

In order to avoid creating orphan devices / nodes 
/ controllers  and moving about devices / nodes / 
controllers during the initial network start-up, it is 
recommended that the same power up sequence initially 
used for the survey be used. 

Please note that once a device / node / controller has 
been assigned a ZigBee address and has joined the 
active ZigBee network, it will save it’s assigned ZigBee 
address to fl ash memory and re-use it afterwards even 
after a power failure or a network re-start. The ONLY time 
device / node / controller would require a NEW ZigBee 
address is if the network is re-started with either a new 
PAN ID or a new Channel value. This causes the currently 
assigned and saved ZigBee address in fl ash to be erased  
and will force the / node / controller to try to re-join a 

A

A

B

B

A

B

Jace

Coordinator

Proposed

location

Ma

x

i

m

u

m

 linear distance covered by a single Jace-Coordinator

20

%

20

%

20

%

20

%

20

%

Fig. 14

 
5.  Leave survey tool B at this location and move survey 

tool A towards the other clusters of controllers. 
Locate the boundary where the signal strength is 
about 20%. This represents the maximum radius 
of the second hop where connectivity is possible 
based on the building environment and partition 
construction.

6.  Repeat the process until you establish the maximum 

range covered by 5 hops where the last position 
recorded represents the “safest” furthest position 
that can be covered by a single Jace – coordinator 
(

fig. 14

).

7.  If more than 5 devices / nodes / controllers are 

present in the same area where readings were taken, 

IT IS RECOMMENDED

 that another Jace coordinator 

be used (

fig. 15

).

 
 

Fig. 15

A

A

B

B

A

B

Jace

Coordinator

Proposed

location

20

%

20

%

20

%

20

%

20

%

Channel 25 Pan ID=20

A

A

B

B

A

B

Jace

Coordinator

Proposed

location

20

%

20

%

20

%

20

%

20

%

Channel 25 Pan ID=10

Содержание VST5000W5028W

Страница 1: ...VST5000W5028W Wireless Survey Tools User Guide August 30th 2010...

Страница 2: ...nal Strength Indicator Please note that it is normal for the value to fluctuate slightly up to 10 20 The final reading value is representative of the median averaged values displayed Any value from 10...

Страница 3: ...plications such as going through stair ways but the design and optimization of the thermostat antenna is designed for optimal horizontal distance penetration and not a vertical one As such be prepared...

Страница 4: ...at at least one thermostat is within 50 feet 15 M of the VWG for every cluster of 10 thermostats installed Always install the VWG closest to the center of all associated wireless thermostats Always lo...

Страница 5: ...installed If possible perform the survey during occupied hours where other electronic devices such as computers wireless laptop cell phones PDA s wireless telephones microwave ovens light ballasts etc...

Страница 6: ...ge radius of the coordinator VWG or Jace Driver at it s proposed location It s possible that another location may improve your network performance or that you may require an additional coordinator VWG...

Страница 7: ...t t Fig 11 5 Then find the potential coverage radiuses through a few of the thermostats furthest away from the coordinator VWG or Jace Driver covered radius fig 10 6 Once the most difficult connectivi...

Страница 8: ...from a parent device This ZigBee address is a value which is NOT initially exposed or available for the integrator to see Devices nodes controllers can calculate and assign addresses for their surrou...

Страница 9: ...te ZigBee addresses to the other devices in building B Within Range Jac t t t t t t t t t t t t t t Jace Building A Building B Fig 12 5H stands for 5 hops maximum ANY given device node controller shou...

Страница 10: ...and will force the node controller to try to re join a A A B B A B Jace Coordinator Proposed location Maximum linear distance covered by a single Jace Coordinator 20 20 20 20 20 Fig 14 5 Leave survey...

Страница 11: ...the information contained therein is solely at the risk of the user Documentation may include technical or other inaccuracies or typographical errors Vykon reserves the right to make changes to this...

Страница 12: ...VYKON 3951 Westerre Parkway Suite 350 I Richmond VA 23233 I USA Phone 804 747 4771 I Fax 804 747 5204 contact tridium com I www vykon com 028 0318 R0...

Отзывы: