background image

5  

VST5000W5028W

 Wireless Survey Tools User Guide 

is designed for optimal horizontal distance 
penetration. Holding the survey tool or the 
thermostat horizontally will dramatically lower the 
range of connectivity.

•  Hold the survey tool at the location where you 

would like to install the thermostat. The closer the 
survey tool is to the actual installation location of the 
thermostat, the more accurate the survey results 

 will 

be.

•  Do NOT stand directly in between 2 survey tools 

while measuring. Your body will interfere with 
transmission signals. Always stand out of line of sight 
to avoid interfering with the signal readings.

•  To insure accurate readings, 

ALWAYS hold the tools 

by the bottom using the battery holder 

(

fi g. 6

). 

Do not hold it by the thermostat case

, as you may 

cover the antenna 

 

(

fig. 7

).

 Important Notes About The Survey Tools:

•  The survey tools feature an auto-shutdown after 

10 minutes. After 10 minutes, 10 quick audio beeps 
will be heard; if the ON button is not re-pressed, the 
unit after the count of 10 beeps, the unit will self 
shutdown to prevent unnecessary battery drainage.

•  The minimal expected battery life is at least 50 full 

charge cycles. The maximum expected battery life is 
200 full charge cycles.

•  Contact Vykon for replacement batteries. The survey 

tools use a custom rechargeable battery type. 

DO NOT USE

 regular rechargeable batteries for 

replacement; the charging circuit is 

NOT DESIGNED 

for that. Doing so MAY result in critical failure and / 
or injury.    

Site Survey Overview  

 

 

If available, it is best to have a fl oor plan layout showing 
the location of all the proposed thermostats to be 
installed.

If possible, perform the survey during occupied hours 
where other electronic devices such as (computers, 
wireless laptop, cell phones, PDA’s, wireless telephones, 
microwave ovens, light ballasts, etc.) would be in use as 
to generate as much interference as possible. 

Some of these devices can generate interference up to 
20 feet or 6.8 meters away during normal operation. Even 
with possible sources of signal interference, the presence 
of these wireless devices will most probably not result in 
any network performance degradation.

It is important to understand that the survey values given 
by the survey tool are provided as a worst case scenario 
of a point to point application. 

Once the whole is deployed with a Jace and VWG 
coordinator and all wireless thermostats are present 
and functioning as routers, the ability of the network to 
effi

  ciently route wireless signals cannot be compared to 

this simple survey analysis method. Thus, it is important 
to remember that the displayed percent signal ONLY 
represents the signal strength from point A to point B. 
As other devices join the network mesh, the route taken 
from device A to device B will most likely change.

A dense cluster of wireless thermostats will allow your 
network to recover from temporary disturbances more 
swiftly.

To ensure a proper survey, Vykon recommends 
using ONLY channels 15 or 25 to avoid network 
interference with 802.11 Wi-Fi devices in the 
2.4GHz spectrum range. Begin by setting BOTH 
devices to the SAME channel & PAN ID. 

Before starting a site survey:

•   Press the on button on both devices while holding 

them side by side. 

•   100% signal strength indicates that the survey tools 

are functioning properly.

Survey Considerations:

•  Always hold the survey device vertically to insure 

proper measurements. The thermostats antenna 

Fig. 6

Fig. 7

Содержание VST5000W5028W

Страница 1: ...VST5000W5028W Wireless Survey Tools User Guide August 30th 2010...

Страница 2: ...nal Strength Indicator Please note that it is normal for the value to fluctuate slightly up to 10 20 The final reading value is representative of the median averaged values displayed Any value from 10...

Страница 3: ...plications such as going through stair ways but the design and optimization of the thermostat antenna is designed for optimal horizontal distance penetration and not a vertical one As such be prepared...

Страница 4: ...at at least one thermostat is within 50 feet 15 M of the VWG for every cluster of 10 thermostats installed Always install the VWG closest to the center of all associated wireless thermostats Always lo...

Страница 5: ...installed If possible perform the survey during occupied hours where other electronic devices such as computers wireless laptop cell phones PDA s wireless telephones microwave ovens light ballasts etc...

Страница 6: ...ge radius of the coordinator VWG or Jace Driver at it s proposed location It s possible that another location may improve your network performance or that you may require an additional coordinator VWG...

Страница 7: ...t t Fig 11 5 Then find the potential coverage radiuses through a few of the thermostats furthest away from the coordinator VWG or Jace Driver covered radius fig 10 6 Once the most difficult connectivi...

Страница 8: ...from a parent device This ZigBee address is a value which is NOT initially exposed or available for the integrator to see Devices nodes controllers can calculate and assign addresses for their surrou...

Страница 9: ...te ZigBee addresses to the other devices in building B Within Range Jac t t t t t t t t t t t t t t Jace Building A Building B Fig 12 5H stands for 5 hops maximum ANY given device node controller shou...

Страница 10: ...and will force the node controller to try to re join a A A B B A B Jace Coordinator Proposed location Maximum linear distance covered by a single Jace Coordinator 20 20 20 20 20 Fig 14 5 Leave survey...

Страница 11: ...the information contained therein is solely at the risk of the user Documentation may include technical or other inaccuracies or typographical errors Vykon reserves the right to make changes to this...

Страница 12: ...VYKON 3951 Westerre Parkway Suite 350 I Richmond VA 23233 I USA Phone 804 747 4771 I Fax 804 747 5204 contact tridium com I www vykon com 028 0318 R0...

Отзывы: