11
VST5000W5028W
Wireless Survey Tools User Guide
new network. I.E. this is ONLY applicable during the initial
network start-up.
1. First power up the orange devices / nodes /
controllers in sequence as showed and wait until
they are joined to the network or matched to
their offl
ine created counterparts ( see the device
management section in this manual on how to
create offl
ine devices / nodes / controllers & match
them to discovered devices ).
2. All the remaining yellow devices / nodes / controllers
can now all be powered up to also join the network.
3. This start-up sequencing allows for ALL devices to be
discovered without creating orphan nodes (
fig. 16
).
Jace
Coordinator
Proposed
location
Power
#1
Power
#2
Power
#3
Power
#4
Power
#5
Power
#6
t
t
t
t
t
t
t
t
t
t
t
t
t
t
t
t
t
t
t t
t
t
t t
t
t
t
t
t t
t
t
t
t
t
t
t
Fig. 16
Points to Remember:
• Always write your transmission results on a plan
when possible.
• Use REP5000W repeaters if remote devices are too
far to bridge or the signal is too weak.
• You can move the coordinator (VWG or Jace-Driver)
to a new location if it helps create better clusters of
thermostats.
• You “should” always plan for a fl oor by fl oor
horizontal architecture vs. a vertical one.
• Additional coordinator (VWG or Jace-Driver) can
be used when clusters become too far apart in an
installation.
• You can always call Vykon technical support for
recommendations if you have a fl oor plan layout
available for review.
Disclaimer
NO WARRANTY.
Vykon (herein after referred to as
“Vykon”) makes no warranty as to the accuracy of or
use of this technical documentation. Any use of the
technical documentation or the information contained
therein is solely at the risk of the user.
Documentation may include technical or other
inaccuracies or typographical errors. Vykon reserves
the right to make changes to this document without
prior notice, and the reader should in all cases consult
Vykon to determine whether any such changes have
been made. The information in this publication does
not represent a commitment on the part of Vykon.
Vykon shall not be liable for incidental or
consequential damages resulting from the furnishing,
performance, or use of this material.
Electronic controls are static sensitive devices.
Discharge yourself properly before manipulation and
installing the Vykon wireless gateway.
Vykon may not be held liable for continued reliable
or robust operation of any and all wireless based
devices. Although Vykon has taken many precautions
in assuring the robustness of the VT7000 series
wireless thermostat product line and associated
network access point. Please note; future application
of additional wireless devices utilizing the same or
similar channels and / or frequencies may degrade
performance of overall system and / or reliability.
Non-approved modifi cations or changes made to
the Wireless Communication Card VWG or wireless
thermostats may void the FCC compliance of the
VWG and wireless thermostats.
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC
RULES. OPERATION IS SUBJECT TO THE FOLLOWING
TWO CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE
HARMFUL INTERFERENCE, AND (2) THIS DEVICE MUST
ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING
INTERFERENCE THAT MAY CAUSE UNDESIRED
OPERATION.
NOTE:
THE MANUFACTURER IS NOT RESPONSIBLE
FOR ANY RADIO OR TV INTERFERENCE CAUSED BY
UNAUTHORIZED MODIFICATIONS TO THIS EQUIPMENT.
SUCH MODIFICATIONS COULD VOID THE USER’S
AUTHORITY TO OPERATE THE EQUIPMENT.