Settings view
You can switch from the performance view to the settings view by pressing the push button. The LEDs indicate the actual setting.
The settings view shows which mode controls the circulator. No settings can be made at this stage. After 2 seconds, the display
switches back to performance view.
If LED 1 is green, it indicates operation or internal control. If LED 1 is red, it indicates alarm or external control. LED 2 and 3 indicate
the different control modes and LED 4 and 5 indicate the different speeds.
LED 1
LED 2
LED 3
LED 4
LED 5
Proportional pressure
Green
+
Constant pressure
Green
+
Constant curve
Green
+
+
Speed 1
Speed 2
+
Speed 3
+
+
Key lock function
The purpose of the key lock function is to avoid accidental change of settings and misuse. When the key lock function is enabled, all
long key presses will be ignored. This prevents the user from entering the "select setting mode" area and allows the user to see the
"show setting mode" area. If you press the key lock for more than 10 seconds, you can toggle between enabling/disabling the key
lock function. When doing so, all LEDs, except for the red LED, will flash for a second indicating that lock is toggled.
UPML 25-95 AUTO and UPMXL 25-105 AUTO -
The user interface allows to select between 6 control
curves in two control modes:
• three proportional pressure curves (PP)
• three constant pressure/power curves (CP).
LED indication of the curve setting
CP and PP curves
Factory presetting
Proportional pressure curve, PP2:
• Push the button for two seconds:
–
Pump goes to setting mode - LED starts flashing.
• With each push, the setting changes:
–
LED 1-2-3 are permanently on, and then the
control curve and mode is changed.
• Flashing mode:
–
Fast: Proportional pressure
–
Slow: Constant pressure/power
• After ten seconds not pushing the button:
–
Setting is adapted.
–
Pump returns to operating mode
• LED 1 or 2
or 3 is permanently on.
–
Pump is running with the selected curve and
mode.
For detailed information refer to the pump supplier documentation.
Maintenance of the pump group comes to periodic checking and cleaning of strainer filter.